8.3.6 Output status setting for CPU module STOP

When the CPU module mounted with a Simple Motion module is set to STOP, whether cyclic
data output is held or cleared can be selected.
(1) Range where the setting becomes enabled
(2) Setting method
(3) Precautions
The setting is fixed to hold or clear depending on devices set to link refresh, regardless
of the output setting during CPU STOP.
The following table shows the relationship between the output status of the device set to
link refresh and output setting during CPU STOP.
Link refresh device
Y
RY
Other devices
All devices where the output setting
RWw
during CPU STOP can be set
Set the output status for the case where the CPU module switch is set to STOP. Select
hold or clear in the "Network Operation Settings" window. (Refer to Section 7.5.)
(a)
When the output setting during CPU STOP is set to clear
When the CPU module is in the STOP status, the forced output to slave stations
cannot be executed using GX Works2.
(b)
When refreshing data by a link direct device
The output status of when the CPU module is set to STOP is the status set for the
network operation settings.
Output setting during CPU STOP
8 - 18
Chapter 8 FUNCTIONS
Hold
Clear (ALL OFF)
Clear
Hold
Hold
Clear
Clear
Hold