Mitsubishi Electric MELSEC-Q Series User Manual page 249

Simple motion module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Number
Name
CPU RUN status (each
SB00F0
station)
CPU RUN status
SB00F1
(master station)
CPU operation status
SB0100
(each station) (1)
CPU operation status
SB0101
(master station) (1)
CPU operation status
SB0110
(each station) (2)
CPU operation status
SB0111
(master station) (2)
Stores the RUN status of each station's CPU module.
OFF: All stations are in RUN or STEP-RUN status
ON: Station in STOP or PAUSE status found
If a station in STOP or PAUSE status is found, the status of each station can be checked by the
CPU RUN status (each station) (SW00F0 to SW00F7).
Depending on the timing of the link refresh, the update of CPU RUN status (each station)
(SW00F0 to SW00F7) may be offset by one sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Stores the RUN status of the master station's CPU module.
OFF: RUN or STEP-RUN status
ON : STOP or PAUSE status
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Stores the stop error status for each station.
OFF: All stations normal
ON : Station with stop error found
If a station with a stop error is found, the status of each station can be checked by the Operation
status (each station) (1) (SW0100 to SW0107).
Depending on the timing of the link refresh, the update of Operation status (each station) (1)
(SW0100 to SW0107) may be offset by one sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Stores the stop error status of the master station's CPU module.
OFF: Normal
ON : Stop error occurred
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Stores the continuation error status for each station.
OFF: All stations normal
ON : Station with continuation error found
If a station with a continuation error is found, the status of each station can be checked by the
Operation status (each station) (2) (SW0110 to SW0117).
Depending on the timing of the link refresh, the update of Operation status (each station) (2)
(SW0110 to SW0117) may be offset by one sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Stores the continuation error status of the master station's CPU module.
OFF: Normal
ON : Continuation error occurred
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Appendix - 13
Description
Appendices