(2) Function
(a)
REMTO instruction overview
The instruction writes data by the specified number of words (n5) from the own
station start device (S) into the buffer memory (after (n4)) of the intelligent device
station/remote device station.
Specify the target stations in setting data ("Jn"/Jn), (n2), and (n3).
When the writing of data is completed, the completion device (D) turns on.
[Own station]
CPU module
(S)
REMTO
(b)
Target stations which can be specified
For details on target stations which can be specified, refer to the following.
Refer to Section 10.1 (1).
(c)
Checking the execution status of the REMTO instruction
The execution status (completion or error) of the REMTO instruction can be
checked using the following device specified for the setting data.
• Completion device (D)
It is turned on in the END processing of the scan after completion of the
REMTO instruction, and is turned off in the next END processing.
• Completion status indication device ((D)+1)
It is turned on in the END processing of the scan after completion of the
REMTO instruction, and is turned off in the next END processing only if the
REMTO instruction fails.
Chapter 10 DEDICATED INSTRUCTIONS
Simple Motion
module
Channel 1
Channel n
Channel 32
10 - 45
[Target station]
Head module
Intelligent function
n4
module
n5
words