Number
SB0002
System link start
SB0003
System link stop
SB0054
System link start request accept status
SB0055
System link start completion status
SB0056
System link stop request accept status
SB0057
System link stop completion status
(Cyclic transmission restart)
8) Specify the station to restart cyclic transmission in the following link special
registers (SWs).
• Specifying a target station
Link stop/start direction (SW0000)
• Specifying a station number
Link stop/start direction (SW0002 to SW0008)
9) Turn on System link start (SB0002).
10) When the Simple Motion module accepts the request, System link start
request accept status (SB0054) turns on.
11) When cyclic transmission restart is completed, System link start completion
status (SB0055) turns on.
12) If cyclic transmission is restarted with error, an error code will be stored in
Data link start status (entire system) (SW0052).
13) Turn off System link start (SB0002).
Description
Number
SW0000
Link stop/start direction
SW0002 to
Link stop/start direction
SW0008
SW004A
Data link stop request station
SW0052
Data link start status (entire system)
SW0053
Data link stop status (entire system)