Number
Name
SW0110
Operation status (each
to
station) (2)
SW0117
SW0120
PORT1 error frame
to
reception status (each
SW0127
station)
Stores the continuation error status for each station.
0: Normal
1: Continuation error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0110
16 15 14 13 12 11 10
SW0111
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0112
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0113
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW0114
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW0115
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW0116
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
__
__
__
__
__
SW0117
Each number in the table represents a station No.
__
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• Holds the data immediately before the error.
• This is enabled only for normal stations in Baton pass status (each station) (SW00A0 to
SW00A7).
• Reserved stations and stations higher than the maximum station No. are ignored.
Stores the station number receiving an error frame on the transmission path at each station's
PORT1.
0: A line error has not yet occurred on the transmission path of each station's PORT1.
1: A line error has occurred on the transmission path of each station's PORT1.
When Clear communication error count (SB0006) is turned on, the stored status is cleared.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0120
16 15 14 13 12 11 10
SW0121
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0122
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0123
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW0124
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW0125
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW0126
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
__
__
__
__
__
SW0127
Each number in the table represents a station No.
__
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• Holds the data immediately before the error.
• This is enabled only for normal stations in Baton pass status (each station) (SW00A0 to
SW00A7).
Appendix - 24
Description
9
8
7
6
5
4
__
__
__
120 119 118 117 116 115 114 113
is fixed to 0.
9
8
7
6
5
4
__
__
__
120 119 118 117 116 115 114 113
is fixed to 0.
Appendices
3
2
1
3
2
1