(7) Checking CPU module status
Number
SB00F0
CPU RUN status (each station)
SB00F1
CPU RUN status (master station)
SB0100
CPU operation status (each station) (1)
SB0101
CPU operation status (master station) (1)
SB0110
CPU operation status (each station) (2)
SB0111
CPU operation status (master station) (2)
Number
SB004A
Own station's CPU status (1)
SB004B
Own station's CPU status (2)
SB004C
CPU RUN status (own station)
The CPU module status is checked using the CC-Link IE Field Network diagnostics as
well as link special relays (SBs) and link special registers (SWs). (Refer to Chapter 9.)
(a)
Checking the CPU module status (other stations)
1) Whether the CPU module is in RUN or STOP can be checked using the
following link special relays (SBs) and link special registers (SWs).
• CPU RUN status (master station) (SB00F1)
• When CPU RUN status (each station) (SB00F0) is turned on, check the
station number using CPU RUN status (each station) (SW00F0 to SW00F7).
2) A continuation error in the CPU module can be checked using the following
link special relays (SBs) and link special registers (SWs).
• CPU operation status (master station) (2) (SB0111)
• When CPU operation status (each station) (2) (SB0110) is turned on, check
the station number using Operation status (each station) (2) (SW0110 to
SW0117).
3) A stop error in the CPU module can be checked using the following link
special relays (SBs) and link special registers (SWs).
• CPU operation status (master station) (1) (SB0101)
• When CPU operation status (each station) (1) (SB0100) is turned on, check
the station number using Operation status (each station) (1) (SW0100 to
SW0107).
Description
(b)
Checking CPU module status (own station)
1) Whether the CPU module is in RUN or STOP can be checked using CPU
RUN status (own station) (SB004C).
2) If a continuation error occurs in the CPU module, Own station's CPU status (1)
(SB004A) turns on.
If a stop error occurs in the CPU module, Own station's CPU status (2)
(SB004B) turns on.
3) The CPU module status can be checked using Own station's CPU status
(SW004B).
Description
Number
SW00F0 to
CPU RUN status (each station)
SW00F7
SW0100 to
Operation status (each station) (1)
SW0107
SW0110 to
Operation status (each station) (2)
SW0117
Number
SW004B
Own station's CPU status
11 - 21
Chapter 11 PROGRAMMING
Description
Description