Zp.remto (Writing Data To The Intelligent Device Station/Remote Device Station); Zp.remto; (Writing Data To The Intelligent Device Station/Remote Device Station) - Mitsubishi Electric MELSEC-Q Series User Manual

Simple motion module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

10.9 ZP.REMTO (Writing Data to the Intelligent Device Station/Remote Device Station)

This instruction writes data to the buffer memory of the intelligent device station/remote
device station. (In units of words)

ZP.REMTO

Setting data
Internal device
(Note-1)
(System, user)
Bit
n1
n2
n3
n4
(S)
n5
D
(Note-1): Local devices and file registers set for each program cannot be used.
(1) Setting data
Start contact
ZP.REMTO
Link direct device
File
register
J \
R, ZR
Word
Bit
Setting data
"Jn"/Jn
Target network No. (1 to 239)
n1
Channels used by own station (1 to 32)
n2
Target station No. (1 to 120)
•Head module
The start I/O number of the intelligent function module (00
to FEH: Upper two digits of the I/O number expressed in
n3
three digits)
•Module other than a head module
Fixed to 00
The start address of the buffer memory of the intelligent
n4
device station/remote device station where data is written
Start device of the own station where data to be written is
S
stored
n5
Number of write points (1 to 240 words)
Device of the own station, which is turned on for 1 scan
D
upon completion of the instruction
(D)+1 is turned on as well when the instruction fails.
Chapter 10 DEDICATED INSTRUCTIONS
Jn
or
n1
n2
"
"
Jn
Available devices
Intelligent function
module device
U \G
Word
Description
10 - 44
n3
n4
(S)
n5
Constant
Index register
Zn
K, H
Set by
User
System
(D)
Others
$
Data type
String/16-bit
binary
16-bit binary
Device name
16-bit binary
Bit

Advertisement

Table of Contents