(Setting range)
Device
Device
Code
No.
0H to
Level Detect and ON : Interrupt occurs by turning
RX
1FFFH
on the device.
Level Detect and OFF: Interrupt occurs by turning off
0H to
RY
the device.
1FFFH
Edge Detect and ON : Interrupt occurs at the rising
edge of the device.
0H to
SB
Edge Detect and OFF: Interrupt occurs at the falling
1FFH
edge of the device.
0H to
Level Detect and Equal: Interrupt occurs when
RWr
3FFH
values match.
Level Detect and Unequal: Interrupt occurs when
0H to 3FF
RWw
values do not match.
H
Edge Detect and Equal: Interrupt occurs when values
match (first time only).
0H to
SW
Edge Detect and Unequal: Interrupt occurs when
1FFH
values do not match (first time only).
RECVS
This item cannot be set for the Simple Motion module.
Instruction
( Note-1): If the value outside the setting range is set, "Parameter error (error code: D62CH)" will occur, and the corresponding interrupt
setting will be invalid.
Detection Method
Interrupt Condition
5) After the parameters are set, open the "Intelligent Function Module Interrupt
Pointer Setting" window.
Link the interrupt (SI) number assigned for the Simple Motion module to the
interrupt pointer of the CPU module.
Project window
[Interrupt Pointer Setting] button
Word Device
Setting Value
0 to 65535
(0H to FFFFH)
[Parameter]
[PLC Parameter]
7 - 26
Chapter 7 PARAMETER SETTING
Channel No./
Connection No.
[PLC System]
Interrupt
(SI) No.
0 to 15