Setting procedure
The user should make the following steps in respective IEDs.
1)
Set BI for the setting [Time Sync Src]; then set On for the setting [BI-SYNC].
2)
Check BI is shown under the ActivSyncSrc, as shown in Figure 5.7-8.
3)
Set a Data_ID for setting [BI_ID]. For example, as shown in the Figure 5.7-7, when
the user wishes to inject the signal at the BI1 on the IO#1 slot, the user should set
BI1(200B01 8001001111) for the setting [BI_ID].
4)
Set a time adjuster for the setting [SYNC ADJ]. For example, set a value (e.g., −0.050s)
for setting [SYNC ADJ]. The setting is used when the clock function should be
synchronized before reaching the 1Hz square-wave due to the propagation or the
operating time on the BI circuit.
Table 5.7-3 Setting items for the BI Time synchronization
Setting item
Range
TimeSyncSrc
SNTP / BI / IRIG-B
BI-SYNC
Off /On
BI_ID
[Preferred ID]
SYNC ADJ
−0.050 to +0.050
Clock
10:00
1/2
[Time]
+
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
BI
Check "BI " being shown under ActiveSyncSrc.
Figure 5.7-8 Time setting for BI
Contents
Selection of sync method
Operation of BI
Signal monitoring point
Time adjust factor (in
sec.)
- 979 -
Setting example
BI
On
200B01 8001001111
0.000
+:Delaying the clock
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)
Notes
−:Leading the clock