Object_reference
Ctrl/GGIO1301$ISCSO1$origin
Ctrl/GGIO1301$ISCSO1$origin
Ctrl/GGIO1301$ISCSO1
Ctrl/GGIO1301$ISCSO1
Ctrl/GGIO1301$ISCSO1
Ctrl/GGIO1301$ISCSO1
Ctrl/GGIO1301$AnIn1$mag
Ctrl/GGIO1301$AnIn1
Ctrl/GGIO1301$AnIn1
Note: "Status (ST)" and "Measurement (MX)" are defined in the function constraint (FC)
of the IEC 61850 standard.
Figure 4.5-6 orCat attribute mapped into ISCSO1 object of GGIO1301
Mapping input data
(iii)
The TTIM01 function can receive three commands "select, operate, and cancel. Thus, the user
will need to map the input-point "TOTAL01_CMM_REQ ". Table 4.5-5 shows the input-point
" TOTAL01_CMM_REQ " and the Object reference "Ctrl/GGIO1301$ISCSO1$" ; the user should
map the input-point to the Object reference having attributes CO and CF in FC† . Figure 4.5-7
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; "CO" stands for "Control"
and "CF" stands for "Configuration" in the functional constraint (FC).
Table 4.5-4 Mapping signals for ISCSO1 object.
Attribute
orCat
orCategory
orIdent
Octet64
stVal
INT32
q
Quality
t
Timestamp
stSeld
BOOLEAN
f
FLOAT32
q
Quality
t
Timestamp
Type
FC
Signal Number
ST
5410013015011D23
ST
5410016A15011FA7
ST
5410013215011D20
ST
5410013115011D21
ST
5410019015011D22
ST
5410010015011D91
MX
5410013215011D20
MX
5410013115011D21
MX
5410019015011D22
- 667 -
6F2S1915 (0.46)
Signal Name
TTIM01_TIM_ORCAT
TTIM01_TIM_ORIDENT
TTIM01_TIM_SEC_VAL
TTIM01_TIM_QLT
TTIM01_TIM_TIM
TTIM01_TMP_01
TTIM01_TIM_SEC_VAL
TTIM01_TIM_QLT
TTIM01_TIM_TIM
Drag and drop
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for: