SPAR+TPAR logic – settings (TSPAR1,TTPAR1,and TRR1)
(x)
The SPAR&TPAR logic for CB#1 and CB#2 is illustrated in Figure 2.24-17. As for the CB#1,
the dead timers [TSPAR1] and [TTPAR1] should be set in the coordination with the [TRR1].
Always '1'
From VCHK function
ARC1-VCHK
ARC2-VCHK
Condition in CB#1
ARC1_SPAR_COND
ARC1_TPAR_COND
From Initiation
ARC1 IN-PROG
ARC1-S1 IN-PROG
Condition in CB#2
ARC2_SPAR_COND
ARC2_TPAR_COND
From Initiation
ARC2-S1 IN-PROG
From Reclose sequence
TPAR1_START
TPAR2_START
Note: Settings [TSPAR1_SUB], [TSPAR2_SUB], [TTPAR1_SUB], [TTPAR2_SUB] are not
required as in the default.
&
800001EBB9
800001EBBA
800001EBBB
800001EBBC
&
810001EBBD
810001EBBE
810001EBBF
810001EBC0
&
800001EBB9
800001EBBA
800001EBBB
800001EBBC
&
810002EBBE
810002EBBF
810002EBC0
810002EBC1
Figure 2.24-19 ARC1 SPAR&TPAR and ARC2 SPAR
&
SPAR1_START
SPAR1_COND
&
SPAR1_SUB_START
SPAR1_SUB_COND
&
TPAR1_START
TPAR1_COND
&
TPAR1_SUB_START
TPAR1_SUB_COND
&
SPAR2_START
SPAR2_COND
&
SPAR2_SUB_START
SPAR2_SUB_COND
&
TPAR2_START
TPAR2_COND
&
TPAR2_SUB_START
TPAR2_SUB_COND
TRR1
t
0.01 – 310.00 s
- 366 -
6F2S1915 (0.46)
TSPAR1
8000011B63
t
0
0.01 – 300.00 s
&
≥1
TSPAR1_SUB
t
0
0.01 – 300.00 s
&
TTPAR1
8000011B63
t
0
0.01 – 300.00 s
&
≥1
TTPAR1_SUB
t
0
&
0.01 – 300.00 s
TSPAR2
8000021B63
t
0
0.01 – 300.00 s
&
≥1
TSPAR2_SUB
t
0
0.01 – 300.00 s
&
TTPAR2
8000021B64
t
0
0.01 – 300.00 s
&
≥1
TTPAR2_SUB
t
0
&
0.01 – 300.00 s
0
ARC1 TRR
ARC1-FT
TRR2
t
0
ARC2 TRR
ARC2-FT
0.01 – 310.00 s
GRZ200 (Soft 031 & 032)
Issuing for CB#1
ARC1_SPAR
ARC1_TPAR
Issuing for CB#2
ARC2_SPAR
ARC2_TPAR
To TRC
CB1_94TT
CB2_94TT

Advertisement

loading

This manual is also suitable for: