Toshiba GR200 Series Instruction Manual page 565

Hide thumbs Also See for GR200 Series:

Advertisement

Setting
4.1.6
SPOS01 (FunctionID:510001)
Setting items
Commo n items SPOS-NELD
SPOS-TELD
SPOS-TELR
SPOS01-EN
DEV01 items
SPOS01-DEVNAME
SPOS01-OFFNAME
SPOS01-ONNAME
SPOS01-NOPSG
SPOS01-SPPEN
SPOS01-CTREN
SPOS01-CTRMENU
SPOS01-CTRAHMI
SPOS01-SLBORD
SPOS01-OEXBORD
SPOS01-FEXBORD
SPOS01-OFEXBORD
SPOS01-LGCTRCON
SPOS01-LGSLFFCT
SPOS01-LGEXFFCT
SPOS01-LGFEXOT
SPOS01-LGCNFFCT
SPOS01-PLSM
SPOS01-CPW
SPOS01-RST
SPOS01-APBD
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The SPOS function is available for a 2
omitted the others because their setting tables are the same as the 1
with the exception of the device number.
Range
Unit
0 - 99
- Number of Event lock detect time
1 - 99
s Timer of detect event lock
1 - 99
s Timer of recovery from event lock
Off / On
- SPOS01 switch for Device01
- item name of Dev1
[Preferred text]
- state name of state(off)
[Preferred text]
- state name of state(on)
[Preferred text]
- Normally Open Signal of Dev1
[Preferred Signal]
Off / On
- Automatic event suppression function
Off / On
- control mode (control enable)
Off / On
- control by MENU enable
DIR / SBO
- control action(Direct or SBO)by HMI
- select binary output read data(DataID)
[Preferred Signal]
on direction execute binary output read
-
[Preferred Signal]
data(DataID)
off direction execute binary output read
-
[Preferred Signal]
data(DataID)
on/off direction execute binary output read
-
[Preferred Signal]
data(DataID)
FixedLogic /
- Change logic about control condition
PLC
FixedLogic /
- Change logic about select fail factor
PLC
FixedLogic /
Change logic about execute command fail
-
PLC
factor
FixedLogic /
Change logic about off direction execute
-
PLC
output
FixedLogic /
- Change logic about cancel command fail factor
PLC
Fix / Var / Latch - pulse mode
0.1 - 50.0
s control pulse width
1.0 - 100.0
s response check timer
Process / Bay
- status change origin
- 544 -
Contents
Device and other devices. We have
nd
6F2S1915 (0.46)
Default
Note
10
10
10
Off
SPOS_Dev1
!
Off
!
On
!
Not Assigned
Off
Off
Off
SBO
5100018501011F76
Not Assigned
Not Assigned
Not Assigned
FixedLogic
FixedLogic
FixedLogic
FixedLogic
FixedLogic
Var
1.0
30.0
Process
device table
st
GRZ200 (Soft 031 & 032)