From SOTFSW*1
Command blocking*1
CBK_STATE
Double Command Blocking detected*2
Other devices traveling detected*3
Function "Automatic sequence control" is in progress
ASEQ_MULTI_SEL
From TRC*4
General trip
GEN.TRIP
Additional condition (PLC#1 connection point)
512001 810301EE62
DPOS01IN_TMP_32
User configurable condition (PLC#2 connection point)
512001 800301EE61
DPOS01IN_TMP_31
From Control hierarchy *9 (PLC#3 connection point)
512001 820301ED50
DPOS01IN_TMP_28
From CMNCTRL
Serious error detection
SERI_ERR
Figure 4.8-13 Select condition logic for 'ON/OFF' in DPOS01
Note: "Command Blocking" disables any operation except its own; the "Command
1
Blocking" is initiated by the status "CBK" in a software switch controller
(SOTFSW). The IEC61850 standard defines "Command Blocking" as "CmdBlk".
For more information on "CBK", see Chapter
Software switch controller. See the signal "
Note: "Double Command Blocking" (DCB) is an operation philosophy in the common
2
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as "DCB
RCV OR" in Table 4.8-6. For more information see Chapter
monitoring application
Note: If the event "device-travelling" is detected in the CMNCTRL function, it indicates
3
that another operator is changing the status of a device. Thus, the IED should
inhibit the operation of any device for the duration that the event is detected. The
detected signal is denoted as "Travelling OR" in Table 4.8-6.
Note: If the issue of a trip command is executed by the IED, any control operation is
4
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issues at the output_point "GEN.TRIP" in Table
4.8-6.
Note: Criteria "unmatched conditions" are decided when "Test-bit status" in a command
5
DPOS01 function (Function ID: 512001)
DCB RCV OR
Unmatched condition detected *5
Traveling OR
Event suppression detected *6
= DPOS01_F_QLT_SPP
BI board connection error detected*7
= DPOS01_F_BI_ERR
Command "ON control" received
Command "OFF control" received
DPOS01_3PH_STATE
(512001 3103011001)
[SCDEN]*8
OFF
[DPOS01-LGSLFFCT]
Fixedlogic
[DPOS01-CTREN]
On
Common controls.
:
1≥
(512001 8103011F5F)
(512001 8203011F60)
&
&
received
Appearance of the
controls in the same
direction
Control and monitoring application:
"CBK_STATE" of Table 4.8-6.
- 732 -
6F2S1915 (0.46)
1≥
&
&
To select logic
Select condition
&
&
*10
Control and
GRZ200 (Soft 031 & 032)

Advertisement

loading