at the monitoring point "TPOS01_CC_SS", when the TPOS01 function determines that the
"Local-Cancel" signal is true.
Cancel condition logic
(iii)
Figure 4.9-25 shows the cancel condition logic. As the criteria "Unmatched condition detected"
is connected normally for the cancel condition logic, set Fixedlogic for the scheme switch
[TPOS01-LGCNFFCT].
User configurable condition (PLC connection point)
513001 800401EE69
TPOS01IN_TMP_40
Figure 4.9-25 Logic "Cancel condition" in TPOS01
Note: The criteria "unmatched conditions" are determined when the "Test-bit status" in
1
the 'cancel' command is not identical to the "IED test status", like in Figure 4.9-20.
Note: With the exception of the above 'cancel' logic, there is an operate-condition logic
2
within the TPOS01 function; the operate-condition logic will always checks
conditions. That is, the user is required to set either the "Operate-condition" or the
"cancel-condition" logic.
If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point "User Configurable condition":
Connect the user-customized logic, with the "TPOS01IN_TMP_40", which is listed
in Table 4.9-12.
Set scheme switch [TPOS01-LGCNFFCT] to PLC.
Signal name and number
(iv)
Note: The user should note the following descriptions shown in the column "M/O" in
each table:
"O" indicates that the signal is provided for the optional use.
"M" indicates that the user should map/set/configure using the signal;
"N/A" indicates that the user cannot change the state of the signal.
Table 4.9-12 PLC connection points (Input signal for 'cancel' condition)
Signal Number
513001 800401EE69
513001 800401EE69
513001 800401EE69
TPOS01 function (Function ID: 513001)
Unmatched condition detected *1
[TPOS01-LGCNFFCT]
Fixedlogic
otherwise, the user may experience an operational failure for the default
settings.
Signal Name
Description
TPOS01IN_TMP_40
TPOS1 user configurable cancel condition
TPOS02IN_TMP_40
TPOS2 user configurable cancel condition
TPOS03IN_TMP_40
TPOS3 user configurable cancel condition
- 809 -
6F2S1915 (0.46)
To cancel logic in
1≥
&
TPOS01
&
M/O
O
O
O
GRZ200 (Soft 031 & 032)