Input
Command "Remote-P3-Control"
513001_7004016D08
DEV01_CONTROL_REQ
ILK† condition ("P3") passed
TPOS1-P3
User configurable condition
(PLC#4 connection point)
513001 840401EE58
TPOS01IN_TMP_29
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
513001 820401EE5E
TPOS01IN_TMP_38
Figure 4.9-31 Operate 'P3-control' from the remote-end in TPOS01
†Note: The ILK function can provide the operation criteria for "P3" control.
Note: To identify the input and output signals of the other TPOS logics, see Table
††
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
‡Note: An "operate condition" signal is generated inthe operate-condition logic (Figure
4.9-44) when Fix logic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative "operate-condition" is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative "operate-condition" can be connected to the above logic using
connection point #4 "User configurable condition" That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use "TPOS01IN_TMP_29".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The "Operate failed" signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST]
§§Note: The "TPOS01-PIEX-BO" signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. The "Operate-completed" signal can also be issued from
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
"
TPOS01_P3EC_OK_CSF"
(5513001 8004011E80)
Operate Cmd.
with ILK
condition
&
Operation Cmd.
without ILK
condition
[TPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[TPOS01-LGP3EXOT]
Fixedlogic
[TPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"TPOS01_P3EC_OK_CSF"
(513001 8004011E80)
- 816 -
"
TPOS01_P3EC_OK_CS"
(513001 8404011E83)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2S1915 (0.46)
Output
[TPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"TPOS01_P3EX_BO"
(513001 8204011DD6) §§
&
Assign to BOs
To "Wait for a command"
"
TPOS01_EX_CMP
(5130018004011E93)
Operation Completed
"
"
TPOS01_EX_FFL
[TPOS01-RST]
(513001 8604011E91) ‡‡
0
t
1.0s- 100.0s
Operation Failed
††
GRZ200 (Soft 031 & 032)
"

Advertisement

loading