4.1.7
 Signal monitoring points in SPOS01
SPOS01(FunctionID:510001)
Element ID
Name
8001011DE0
DEV1PLCCTRLFAIL
0001001F74
SPOS_SEL_OR
0001011001
SPOS01_STATE
0001011D90
SPOS01_SLD_RPT
0001011D97
SPOS01_EX_BO_OPOK
0001011F52
SPOS01_TRA
0001011F53
SPOS01_TRA_CTR
0001011F75
SPOS01_SE_RCV
3101011D00
SPOS01_MMC_ST
3101011D01
SPOS01_LCD_ST
3101011D80
SPOS01_TMP_06
3101011D81
SPOS01_TMP_07
3101011D82
SPOS01_TMP_08
3101011D83
SPOS01_TMP_09
3101011D84
SPOS01_TMP_10
3101011D86
SPOS01_TMP_11
8001011D02
SPOS01_ST_OFF
8001011D51
SPOS01_SC_OWS
8001011D52
SPOS01_SC_RCC
8001011D53
SPOS01_SC_RMT
8001011D54
SPOS01_SC_LCD
8001011D55
SPOS01_EC_OWS
8001011D56
SPOS01_EC_RCC
8001011D57
SPOS01_EC_RMT
8001011D58
SPOS01_EC_LCD
8001011D59
SPOS01_EC_PLC
8001011E76
SPOS01_SLD_CS
8001011E7D
SPOS01_SLR_CS
8001011E7E
SPOS01_FEC_OK_CSF
8001011E7F
SPOS01_OEC_OK_CSF
8001011E81
SPOS01_FEC_OK_CS
8001011E93
SPOS01_EX_CMP
8001011F54
SPOS01_SC_ST_ERR
8001011F55
SPOS01_EC_ST_ERR
8001011F56
SPOS01_NSL_CS06
8001011F66
SPOS01_SLD_CS04
8101011D03
SPOS01_ST_ON
8101011DD0
SPOS01_FEX_BO
8101011E7B
SPOS01_SLF_CS
8101011E82
SPOS01_OEC_OK_CS
8101011E85
SPOS01_FEC_F_CSF
8101011E86
SPOS01_OEC_F_CSF
8101011E9A
SPOS01_ECF_FCT_EIS
8101011F59
SPOS01_F_QLT_SPP
8101011F64
SPOS01_FSL_CS21
8201011DD3
SPOS01_OEX_BO
8201011E88
SPOS01_FEC_F_CS
8201011F5A
SPOS01_F_BI_ERR
8201011F5F
SPOS01_NSL_CS10
8301011E89
SPOS01_OEC_F_CS
8301011E9C
SPOS01_CCF_FCT_CS
Description
DEV1PLCCTRLFAIL
SPOS multi select check signal for Auto sequence
SPOS01 state
SPOS01 selected signal(stSeld) for SAS
SPOS01 execute binary output signal for SAS
SPOS01 travelling info
SPOS01 travelling info for control
SPOS01 select or execute command received
SPOS01 state for MIMIC
SPOS01 state for LCD
SPOS01 control event data (selected)
SPOS01 control event data (select fail)
SPOS01 control event data (select release)
SPOS01 control event data (execute output on)
SPOS01 control event data (execute command ng)
SPOS01 control event data (execute fail)
SPOS01 status Off
SPOS01 select command by OWS(HMI)
SPOS01 select command by RCC
SPOS01 select command by Remote
SPOS01 select command by LCD
SPOS01 execute command by OWS(HMI)
SPOS01 execute command by RCC
SPOS01 execute command by Remote
SPOS01 execute command by LCD
SPOS01 execute command by PLC
SPOS01 selected condition signal
SPOS01 select release condition signal
SPOS01 off direction execute command OK condition signal by fixedlogic
SPOS01 on direction execute command OK condition signal by fixedlogic
SPOS01 off direction execute command OK condition signal
SPOS01 execute complete signal
SPOS01 select command mode err
SPOS01 execute command mode err
SPOS01 no direction select condition signal 06
SPOS01 selected condition signal 04
SPOS01 status On
SPOS01 off direction execute binary output signal
SPOS01 no direction select fail condition signal
SPOS01 on direction execute command OK condition signal
SPOS01 off direction execute command fail condition signal by fixedlogic
SPOS01 on direction execute command fail condition signal by fixedlogic
SPOS01 execute command fail factor signal except interlock/synchronism check
TEMP31
SPOS01 off direction select condition signal 21
SPOS01 on direction execute binary output signal
SPOS01 off direction execute command fail condition signal
TEMP32
SPOS01 no direction select condition signal 10
SPOS01 on direction execute command fail condition signal
TEMP21