EF(Function ID:441001)
Setting items
ORG
EF3
EF3-DPR
EF3-TMS-ORG
EF3-Rtimer
TEF3R
EF3-RTMS-
ORG
EF3-k
EF3-a
EF3-c
EF3-kr
EF3-b
Output
EF3-VTFBlk
EF3-CTFBlk
EF3-UseFor
EF3-ARCBlk
EF4
EF4-Dir
Fwd/
EF4-Angle
Rev
EF4-Vpol
EF4-Timer
DT
EF4
EF4-DPR
TEF4
IEC
EF4
EF4-DPR
EF4-TMS-IEC
TEF4R
UK
EF4
EF4-DPR
EF4-TMS-UK
TEF4R
IEEE
EF4
EF4-DPR
EF4-TMS-
IEEE
EF4-Rtimer
TEF4R
EF4-RTMS-
IEEE
US
EF4
EF4-DPR
EF4-TMS-US
Range
Unit
1A rating
5A rating
0.02 -
0.10 -
A EF3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% EF3 drop-out/pick-up ratio
0.010 - 50.000
- EF3 time multiplier of Original inverse curve
DEF / DEP
- EF3 reset delay type of ORG
0.00 - 300.00
s EF3 definite time reset delay
EF3 dependent reset time multiplier of
0.010 - 50.000
-
Original inverse curve
0.00000 - 500.00000
- EF3 user original curve coefficient
0.00000 - 10.00000
- EF3 user original curve coefficient
0.00000 - 10.00000
- EF3 user original curve coefficient
0.00000 - 500.00000
- EF3 user original curve coefficient
0.00000 - 10.00000
- EF3 user original curve coefficient
Non / Block
- EF3 operation block by VTF
Non / Block
- EF3 operation block by CTF
Trip / Alarm
- EF3 used for trip or alarm
Non / Block
- Autoreclose block by EF3
NonDir / Forward /
- EF4 directional characteristic
Reverse
0 - 180
deg EF4 directional characteristic angle
0.5 - 100.0
V EF4 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- EF4 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 -
0.10 -
A EF4 threshold (in DT mode)
50.00
250.00
10 - 100
% EF4 drop-out/pick-up ratio
0.00 - 300.00
s EF4 operating delay time (in DT mode)
0.02 -
0.10 -
A EF4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% EF4 drop-out/pick-up ratio
0.010 - 50.000
- EF4 time multiplier of IEC inverse curve
0.00 - 300.00
s EF4 definite time reset delay
0.02 -
0.10 -
A EF4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% EF4 drop-out/pick-up ratio
0.010 - 50.000
- EF4 time multiplier of UK inverse curve
0.00 - 300.00
s EF4 definite time reset delay
0.02 -
0.10 -
A EF4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% EF4 drop-out/pick-up ratio
0.010 - 50.000
- EF4 time multiplier of IEEE inverse curve
DEF / DEP
- EF4 reset delay type of IEEE
0.00 - 300.00
s EF4 definite time reset delay
EF4 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 -
0.10 -
A EF4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% EF4 drop-out/pick-up ratio
0.010 - 50.000
- EF4 time multiplier of US inverse curve
- 189 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
0.30
1.50
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Trip
Block
NonDir
45
3.0
DT
0.30
1.50
100
1.00
0.30
1.50
100
1.000
0.00
0.30
1.50
100
1.000
0.00
0.30
1.50
100
1.000
DEF
0.00
1.000
0.30
1.50
100
1.000