Toshiba GR200 Series Instruction Manual page 415

Hide thumbs Also See for GR200 Series:

Advertisement

Setting
2.25.7
VCHK(Function ID: 4A8001) at Autoreclose
Setting items
ARC1-VCHK-
EN
ARC2-VCHK-
EN
ARC1 Voltage
check
SYN-Vbus
SYN-Vline
VCHK-OVB
VCHK-UVB
VCHK-OVL
VCHK-UVL
SYN1-Angle
SYN1-dV
SYN1-df
ARC1-LB_DL
ARC1-DB_LL
ARC1-DB_DL
ARC1-SYN1
ARC1-
NOVCHK
T_LB_DL
T_DB_LL
T_DB_DL
T_SYN1
T_OVL3P
ARC2 Voltage
check
SYN-Vline2
VCHK-OVL2
VCHK-UVL2
SYN2-Angle
SYN2-dV
SYN2-df
ARC2-LL2_DL
ARC2-DL2_LL
ARC2-DL2_DL
ARC2-SYN2
Range
Unit
1A rating
5A rating
Off / On
- VCHK1 scheme switch
Off / On
- VCHK2 scheme switch
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1 / V2-L2 / V2-L3
- Running Voltage
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1 / V2-L2 / V2-L3
- Incoming Voltage
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
10 - 150
V Voltage for the checking Live-Bus
10 - 150
V Voltage for the checking Dead-Bus
10 - 150
V Voltage for the checking Live-Line
10 - 150
V Voltage for the checking Dead-Line
0 - 75
deg Difference angle for the checking SYN1
0 - 150
V Difference voltage for the checking SYN1
0.01 - 2.00
Hz Difference frequency for the checking SYN1
Voltage check Live-Bus & Dead-Line is
Off / On
-
applied to ARC1
Voltage check Dead-Bus & Live-Line is
Off / On
-
applied to ARC1
Voltage check Dead-Bus & Dead-Line is
Off / On
-
applied to ARC1
Off / On
- Voltage check SYN1 is applied to ARC1
Off / On
- Voltage check is not applied to ARC1
0.01 - 100.00
s Voltage check time Live-Bus and Dead-Line
0.01 - 100.00
s Voltage check time Dead-Bus and Live-Line
0.01 - 100.00
s Voltage check time Dead-Bus and Dead-Line
0.01 - 100.00
s Voltage check time SYN1
0.01 - 100.00
s Voltage check time 3phase Live-line
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1 / V2-L2 / V2-L3
- Running Voltage
/ V2-L12 / V2-L23 /
V2-L31 / V3 / V4
10 - 150
V Voltage for the checking Live-Line2
10 - 150
V Voltage for the checking Dead-Line2
0 - 75
deg Difference angle for the checking SYN2
0 - 150
V Difference voltage for the checking SYN2
0.01 - 2.00
Hz Difference frequency for the checking SYN2
Voltage check Live-Line2 & Dead-Line is
Off / On
-
applied to ARC2
Voltage check Dead-Line2 & Live-Line is
Off / On
-
applied to ARC2
Voltage check Dead-Line2 & Dead-Line is
Off / On
-
applied to ARC2
Off / On
- Voltage check SYN2 is applied to ARC2
- 394 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
Off
Off
V3
V-L1
51
13
51
13
30
150
1.00
Off
Off
Off
Off
On
0.05
0.05
0.05
1.00
0.05
V4
51
13
30
150
1.00
Off
Off
Off
Off

Advertisement

loading

This manual is also suitable for: