Select logic for SBO/DIR modes
4.4.1
The user should set the scheme switch [OPTR01-EN] to On prior to the OPTIM operation.
Figure 4.4-4 shows select logic in the OPTIM function.
Wait for a command
Select logic
Resetting OTs from the remote-end
Signal reception
IEC61850
Input point required mapping
(i)
Figure 4.4-5 shows the select logic when a "Select command (Reset)" signal enters the OPTIM
function. The logic has the input-point "OPTR01_CONTROL_REQ" for the reception. That is,
the input-point should be mapped for the IEC61850 communication. The function encounters
an operation failure if mapping is not performed correctly. We discuss how to map the input-
points for the IEC61850 communication in section 4.4.4.
Input
Command "Reset"
529001 700C016D08
OPTR01_CONTROL_REQ
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
"Automatic sequence control function
(AQEQ)§" in progress
ASEQ_MULTI_SEL
Figure 4.4-5 Select logic for resetting intervals OT1 to OT4
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.4-6.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
the automatic control. The OPTIM operation is blocked for the ASEQ function
being in the operation. For more information of the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
Selection logic
Figure 4.4-4 Outline of select command for resetting
OPTIM function (Function ID: 529001)
For SBO operation
Select
command
For DIR operation
Operate
command
In SBO operate
In DIR operate
Select condition‡
Failed
Select
Signal output
decision
Success
Select logic in OPTR
OPTR01_FSE_RCV
(529001 800C011F42)
1≥
&
&
&
0
0.2s
0
0.3s
- 649 -
6F2S1915 (0.46)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
Output
OPTR01_NSD_CSF
To "Wait for a next command"
(529001 830C011F41)
t
529001 000C011D90
OPTR01_STSELD
t
Failed
GRZ200 (Soft 031 & 032)
.