Defining DIR mode
Figure 3.8-3 exemplifies the settings in LN "LLNO" when the DIR mode is required for the
MDCTRL01 function. In the DIR mode, the following three items should be selected using the
GR-TIEMS:
Figure 3.8-3 LN editing screen for DIR mode (for example)
Mapping output data
(ii)
The user should group the MDCTRL01 signals with regard to GOOSE and REPORT; the user
should map them for the IEC 61850 communication using GR-TIEMS.
Table 3.8-4 shows the required mapping signals in MDCTRL01 function to the IEC 61850
communications. Figure below shows how to map a signal.
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice "operate-once")
ctlmodel (choice "SBOes or SBOns" )
†"sboClass" can be found by scrolling down.
Oper
origin
ctlmodel (choice "DOes or DOns" )
- 490 -
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)