6F2S1915 (0.46)
fault in response to the "re-trip" command, OCCBF and EFCBF would reset and the CBF
sequence is stopped.
If the target CB were to fail to remove the fault with the "re-trip" command, and if
OCCBF or EFCBF continued to operate and if the timer #2 were to time out in accordance with
the setting time applied [TCBF1-TP], CBF will issue a trip signal to the adjacent CB(s) to clear
the fault, as a last resort.
GRZ200 (Soft 031 & 032)
- 226 -