ZG (Function ID: 431001)
Setting items
Z4G-
Mho.Reach
Z4G-MhoX.EN
Z4G-X.Reach
Z4G-MhoR.EN
Z4G-R.Angle
Z4G-R.Reach
Z4G-
MhoDX.EN
Z4G-DX.Angle
Quad
Z4G-X.Reach
Z4G-R.Angle
Z4G-R.Reach
Z4G-DX.Angle
Z4G-DR.Angle
I0K
Z4G-Krs
Z4G-Kxs
Z4G-Krm
Z4G-Kxm
Z4G-EFL
TZ4G
Output
Z4G-MPFBlk
Z4G-PSBBlk
Z4G-LEBlk
Z4G-LPBlk
Z4G-TPMD
Z4G-ARCBlk
Z4G-OCFS-EN
OCF4G
Z4G-SOTF
Z5G
Z5G-Dir
Mho
Z5G-Mho.Angle
Z5G-
Mho.Reach
Z5G-MhoX.EN
Z5G-X.Reach
Z5G-MhoR.EN
Z5G-R.Angle
Z5G-R.Reach
Z5G-
MhoDX.EN
Range
Unit
1A rating
5A rating
0.10 -
0.01 -
- Z4G mho reach (for Mho)
500.00
100.00
Off / On
- Z4G reactance reach use or not (for Mho)
0.10 -
0.01 -
- Z4G reactance reach
500.00
100.00
Off / On
- Z4G resistive reach use or not (for Mho)
30 - 90
deg Z4G resistive reach characteristic angle
0.10 -
0.01 -
- Z4G resistive reach
500.00
100.00
Z4G directional-X characteristic use or not (for
Off / On
-
Mho)
0 - 60
deg Z4G directional-X characteristic angle
0.10 -
0.01 -
- Z4G reactance reach
500.00
100.00
30 - 90
deg Z4G resistive reach characteristic angle
0.10 -
0.01 -
- Z4G resistive reach
500.00
100.00
0 - 60
deg Z4G directional-X characteristic angle
Z4G directional-R characteristic angle (for
0 - 60
deg
Quad)
0 - 1000
% Zero phase current factor, Self line R0/R1
0 - 1000
% Zero phase current factor, Self line X0/X1
Zero phase current factor, Adjacent line
0 - 1000
%
R0m/R1
Zero phase current factor, Adjacent line
0 - 1000
%
X0m/X1
EFL operation condition used or not for Z4G
Off / On
-
operation
0.00 - 100.00
s Z4G operation delay time
Non / Block
- Z4G operation block or not in multi phase fault
Non / Block
- Z4G operation block or not by PSB detection
Non / Block
- Load encroachment enable
Non / Block
- Z4G leading phase operation block
Z4G trip mode, phase segregated trip or 3-
1P / 3P
-
phase trip
Non / Block
- Autoreclose execution block by Z4G-trip
Off / On
- Fail-safe OC for Z4G-trip
0.10 -
0.02 - 5.00
A Fail-safe OC operation level for Z4G-trip
25.00
Off / On
- SOTF using Z4G
Forward / Reverse /
- Z5G direction to protect
NonDir
30 - 90
deg Z5G mho characteristic angle (for Mho)
0.10 -
0.01 -
- Z5G mho reach (for Mho)
500.00
100.00
Off / On
- Z5G reactance reach use or not (for Mho)
0.10 -
0.01 -
- Z5G reactance reach
500.00
100.00
Off / On
- Z5G resistive reach use or not (for Mho)
30 - 90
deg Z5G resistive reach characteristic angle
0.10 -
0.01 -
- Z5G resistive reach
500.00
100.00
Z5G directional-X characteristic use or not (for
Off / On
-
Mho)
- 99 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
20.00
4.00
Off
20.00
4.00
Off
75
25.50
5.10
Off
30
20.00
4.00
75
25.50
5.10
30
5
100
100
0
0
On
0.60
Non
Non
Non
Non
3P
Block
Off
0.20
1.00
Off
Reverse
85
10.00
2.00
Off
10.00
2.00
Off
75
25.50
5.10
Off

Advertisement