operation of the detection function from Time 'A' (e.g., Time 'A' to Time 'C').
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPSY-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time 'D' to 'E').
To initiate event suppression the user should set On for scheme switch [DPSY01-SPPEN].
BO connection for "select command Open/Closing"
(ii)
Figure 4.2-43 exemplifies the connection for the select command Open/Closing. Suppose that
connection with the BOs is achieved by the PLC function using connection points
"DPSY01_OSL_BO_FLG" and "DPSY01_FSL_BO_FLG"†; as a result, the "Select command
Closing" and the "Select command Open" signals are issued at BO1 and BO2 respectively.
Select logic in DPSY01
Select logic for Select Command
Closing in DPSY01
Select logic for Select Command
Open in DPSY01
Figure 4.2-43 Example for select commands connection with BO1 & BO2 at IO#1
†Note: Table 4.2-10 shows the remaining signals with the excepting
"DPSY01_OSL_BO_FLG" and "DPSY01_FSL_BO_FLG".
BO connection for "operate command Open/Closing"
(iii)
Figure 4.2-44 exemplifies the connection for "Operate command Closing" or "Operate command
Open". Suppose that connection with the BOs is achieved by the PLC function using connection
"
"
DPSY01_OSL_BO_FLG
(5110018602011DC6)
To contact health
check
Connected by
"Programming"
PLC connection point on BO1
"
"
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
To contact health
check
Connected by
"Programming"
PLC connection point on BO2
- 593 -
BO1 circuit at IO#1(Function ID: 200B01)
Signal captured by
≥1
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[BO1_CPL]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
200B01 310200E11D
BO1_SOURCE
BO2 circuit at IO#1 (Function ID: 200B01)
Signal captured by
≥1
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[BO2_CPL]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
200B01 310201E11D
BO2_SOURCE
6F2S1915 (0.46)
Terminal and
wire
"
"
Select
BO1
Command
(
200B01_8002001112)
Closing
DRIVER
BO1
&
≥1
"
"
BO1-RB
On
&
(200B01_8002001113)
Off
To contact health
check
Terminal and
wire
"
"
BO2
Select
Command
(
200B01_8102011112)
Open
DRIVER
BO2
≥1
&
"
"
BO2-RB
On
&
(200B01_8102011113)
Off
To contact health
check