VCHK1 for 1CB system
2.25.1
Characteristic and elements
(i)
VCHK1 does voltage and synchronous check in 1CB system. Four relay elements (OVB, OVB,
UVL, and UVL) are used for voltage check. Tow relay elements (OVB and OVL) are used for
verification of existing voltage; the remaining ones (UVB and UVL) are used for verification of
non-existing voltage.
Voltage condition and check zone
(ii)
Figure 2.25-2 shows four zones (A1 to D1) for voltage verification. For example, if both UVB
and OVL elements are active, VHCK1 determines that the Bus-bar is in Dead condition (no-
voltage) and Line is in Live condition (existing voltage). This condition holds true for A1 zone.
If voltage condition matches with B1 zone, synchronous check is carried out on VCHK1. Thus,
this means that Synchronous check is not carried out in A1, C1 or D1 zones.
VCHK-OVL
VCHK-UVL
Voltage condition
Check zone
Bus-bar voltage (V B )
Line voltage (V L )
V L Line voltage
(Incoming voltage)
Dead bus and
live line
A1
(DB-LL)
Dead bus and
dead line
(DB-DL)
C1
0(V)
VCHK-UVB
Figure 2.25-2 Check zones by VCHK1
Table 2.25-2 Voltage condition by VCHK1
DB_LL
A1
Dead
Live
- 379 -
Live bus and
live line
B1
(LB-LL)
Live bus and
dead line
(LB-DL)
D1
V B Bus-bar voltage
VCHK-OVB
(Running voltage)
A1, C1, D1:
Voltage check
B1:
Synchronism check
LB_LL
DB_DL
B1
C1
Live
Dead
Live
Dead
6F2S1915 (0.46)
LB_DL
D1
Live
Dead
GRZ200 (Soft 031 & 032)