Control logics for SBO/DIR modes
4.3.2
For example, the user should set scheme switch [S4301-EN] to On when the SOFTSW1
function is required to be operated. Table 4.3-10 shows all scheme switches for the SOFTSW
functions.
Receiving "select command for On operation" from the remote-end
(i)
Input point required mapping
Figure 4.3-6 shows the logic when a "Select command (Remote-ON-Control)" signal is applied
to the SOFTSW1 function. The logic has an input-point "S4301_CONTROL_REQ" for the
reception of the select command. That is, the input-point should be mapped for the IEC61850
communication. The input-point "S4301_CONTROL_REQ" is significant for the SOFTSW1
operation; hence, an operation failure in the IED is indicated if mapping is not performed
correctly. Section 4.3.5 discusses how to map the information of the IEC61850 to the input-
points.
Input
Command "Remote-On-Control"
522001_700A046D08
S4301_CONTROL_REQ
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
"Automatic sequence control function (AQEQ)§" in progress
ASEQ_MULTI_SEL
Figure 4.3-6 Select logic for 'ON' operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-6 and Table 4.3-9.
‡Note: "Select condition" signal is provided from select condition scheme. For more
information, see Figure 4.3-12.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SOFTSW1 function is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter
and monitoring application: Automatic sequence control function
*Note: The SOFTSW1 function can run on either the "SBO mode" or the "DIR mode". The
user can use the signal "ctlmodel" in the IEC61850 communication.
510001 7001016D08
Select logic in SOFTSW1
SOTFSW1 function (Function ID: 522001)
For SBO operation
Select command
For DIR operation
Operate command
In SBO operate
In DIR operate
Select condition‡
- 616 -
1≥
&
&
&
0
0
6F2S1915 (0.46)
Output
For monitoring
"S4301_OSD_CSF"
(522001_8F0A041F49)
t
Select "success"
0.1s
To "Wait for a command"
t
Select "Failed"
0.6s
510001 8601011DC
Control
.
GRZ200 (Soft 031 & 032)