Signals from user-PLC logic
P1-control command requiring ILK† check
(PLC connection point #1)
513001 800401EE31
DEV01_P1_INTERLOCK
ILK† condition ("P1") passed
P1-control command not requiring ILK† checking
(PLC connection point #2)
513001 800401EE30
DEV01_P1_COMMAND
Figure 4.9-15 Select 'P1-control' by the PLC function in TPOS01
†Note: The ILK function provides the operation criteria for "P1-control".
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
*Note: The TPOS01 function can run in either the "SBO mode" or the "DIR mode". The
user can use signal called "ctlmodel" when communication is implemented using
IEC61850. To use this signal, the user must map for IEC61850 communication.
Note: To identify the input and output point of the other TPOS logics, see Table 4.9-8
††
for the inputs PLC#1 and PLC#2, Table 4.9-10 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.9-15, can issue a "Select success" signal at the output-point
"TPOS01_P1SL_BO_FLG"
Note: The "TPOS01_P1SL_BO_FLG" signal is the same as the signal shown in Figure
1
4.9-13.
Receiving "Select command P2-control" by PLC function
(viii)
Figure 4.9-16 outlines the reception of the select command 'P2-control' by the PLC function.
TPOS01 function (Function ID: 513001)
For DIR operation
Operate command
with ILK† condition
TPOS1-P1
For DIR operation
Operate command
without ILK† condition
PLC in DIR operate
Select condition‡
.
1
- 797 -
510001 7001016D08
Selection logic in TPOS01
1≥
&
&
6F2S1915 (0.46)
Output
&
To "Wait for a next
command"
To BO connection
"TPOS01_P1SL_BO_FLG"
(513001 8A04011DC4)
0
t
Select "success"
0.1s
To "Wait for a command"
0
t
Select "Failed"
0.6s
††
.
GRZ200 (Soft 031 & 032)