Binary output circuit
5.4.4
Either a CPL logic or a PLC signal can drive a binary output circuit. Table 5.4-9 shows the
settings summary of CPL function.
Setting items
BO1_CPL
BO1
Input signal1
Input signal2
Input signal3
Input signal4
Input signal5
Input signal6
Input signal7
Input signal8
LOGIC-SW
On Delay Timer
Off Delay Timer
INVERSE-SW
TIMER-SW
Logic Timer
Reset signal
BO2_CPL
BO2
Input signal1
.....
Input signal8
LOGIC-SW
On Delay Timer
Off Delay Timer
INVERSE-SW
TIMER-SW
Logic Timer
Reset signal
.....
BO
n
_CPL
n
BO
Input signal1
.....
Input signal8
LOGIC-SW
On Delay Timer
Off Delay Timer
INVERSE-SW
TIMER-SW
Logic Timer
Reset signal
Note: The user can set a reset signal and eight input signals with Data IDs. Data IDs
1
are listed as a signal monitoring point for each function. Setting items are
summarized in each slot. (See sections 5.4.8(i) and 5.4.8(ii))
Table 5.4-9 Setting items for binary output circuits
Setting-range or
Data_ID
Off / On
(Preferred Data ID)
(Preferred Data ID)
(Preferred Data ID)
(Preferred Data ID)
(Preferred Data ID)
(Preferred Data ID)
(Preferred Data ID)
(Preferred Data ID)
AND/OR/XOR
0.000 to 300.000
0.000 to 300.000
Normal / Inverse
OFF/Delay/Dwell/Latch
0.000 to 300.000
(Preferred Data ID)
Off / On
(Preferred Data ID)
.....
(Preferred Data ID)
AND/OR/XOR
0.000 to 300.000
0.000 to 300.000
Normal / Inverse
OFF/Delay/Dwell/Latch
0.000 to 300.000
(Preferred Data ID)
Off / On
(Preferred Data ID)
.....
(Preferred Data ID)
AND/OR/XOR
0.000 to 300.000
0.000 to 300.000
Normal / Inverse
OFF/Delay/Dwell/Latch
0.000 to 300.000
(Preferred Data ID)
Contents
– Switch On for programmable operation
– Set a Data ID at the first input on BO1.
– Set a Data ID at the second input on BO1.
– Set a Data ID at the third input on BO1.
– Set a Data ID at the forth input on BO1.
– Set a Data ID at the fifth input on BO1.
– Set a Data ID at the sixth input on BO1.
– Set a Data ID at the seventh input on BO1.
– Set a Data ID at the eighth input on BO1.
– Switch for logic-gate operation on BO1
s
Set a value for an on-delay-timer on BO1
s
Set a value for an off-delay-timer on BO1
s
Inversion operation of BO1 signal
– Selection of a type in the delay timer on BO1
s
Setting Off Delay Timer for Delay and Dwell
– Setting Data ID for Latch
– Switch On for programmable operation
– Set a Data ID at the first input on BO2.
.....
– Set a Data ID at the eighth input on BO2
– Switch for logic-gate operation on BO2
s
Set a value for an on-delay-timer on BO2
s
Set a value for an off-delay-timer on BO2
– Inversion operation of BO2 signal
– Selection of a type in the delay timer on BO2
s
Setting Off Delay Timer for Delay and Dwell
– Setting Data ID for Latch
– Switch On for programmable operation
– Set a Data ID at the first input on BO
.....
– Set a Data ID at the eighth input on BO
– Switch for logic-gate operation on BO
s
Set a value for an on-delay-timer on BO
s
Set a value for an off-delay-timer on BO
– Inversion operation of BO
– Selection of a type in the delay timer on BO
s
Setting Off Delay Timer for Delay and Dwell
– Setting Data ID for Latch
- 936 -
6F2S1915 (0.46)
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Normal
Not assigned
Not assigned
Not assigned
Normal
Not assigned
n
Not assigned
n
Not assigned
n
n
n
n
signal
Normal
n
Not assigned
GRZ200 (Soft 031 & 032)
Default
Off
1
1
1
1
1
1
1
1
AND
0.000
0.000
OFF
0.000
1
Off
1
.....
1
AND
0.000
0.000
OFF
0.000
1
Off
1
.....
1
AND
0.000
0.000
OFF
0.000
1