Measurement of operation intervals
4.2.5
The DPSY01 function can measure operation intervals (OT1 to OT4)†; the intervals OT1 to
OT2 can represent the period of time when a switch changes from "Closed" to "open". In the
DPSY01 function the operation period is grouped into sub-time periods, as shown in Table
4.2-28. The user should set scheme switch [DPSY01-OPETMEN] to On.
Table 4.2-28 Intervals measured in the DPSY01 function
Intervals
OT1
OT2
OT3
OT4
†Note: The function "operation time measurement" is also available in the DPSY02
function.
Signal "DPSY01_FEX_BO"
Sensing Intermediate state
Device status for Open
Figure 4.2-37 Two intervals (OT1 and OT2) for Open-control
Signal "DPSY01_OEX_BO"
Un sensed period
Device status for Closed
Figure 4.2-38 Two intervals (OT3 and OT4) for Closing-control
The user can clear the operation interval (OT1 to OT4) by key-operation of the "Operation
time" sub-menu (Figure 4.2-39) or operation from the remote-end. See chapter
Trigger Events for measurement
Signal "DPSY01_FEX_BO" sensed
Start
Switch status is changed from "Closed" to
End
"Intermediate"
Switch status "Intermediate" sensed
Start
Switch status is changed from "Intermediate" to
End
"Open"
Signal "DPSY01_OEX_BO" sensed
Start
Switch status is changed from "Open" to
End
"Intermediate"
Switch status "Intermediate" sensed
Start
Switch status is changed from "Intermediate" to
End
"Closed"
Closed
OT1
Open
OT3
- 588 -
Intermediate
Open
OT2
Intermediate
Closed
OT4
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)