Download Print this page

Toshiba GR200 Series Instruction Manual page 935

Hide thumbs Also See for GR200 Series:

Advertisement

Configuration switch
5.3.2
The CPU module has a jumper to change configuration mode (Jumper W6). Figure 5.3-3 shows
the location. For default mode (normal), Pins 1-2 and 3-4 are open (i.e., default configuration
has been set by the manufacture in accordance with the order code). When the user wishes to
alter the other mode particularly, close either Pin 1-2 or Pin 3-4 using a jumper (Optional EP-
221).
CPU
W6
W6
(1-2)
(3-4)
Open
Open
Closed
Open
Open
Closed
Note: Alter the configuration mode before VCT setting. Using GR-TIEMS, the user
needs to rewrite the settings. See
rated current
Jumper
Configuration mode
Default (normal) mode(i.e.,
2-1
4-3
manufacture setting mode )
2-1
Constrained mode (1A rated)
4-3
2-1
Constrained mode (5A rated)
4-3
Figure 5.3-3 Configuration switch
Chapter Installation and setting: Changing
for more detail.
- 914 -
6F2S1915 (0.46)
W5
2-1
4-3
CPM2
W6
2-1
4-3
CPU
W7
2-1
4-3
W8
2-1
4-3
GRZ200 (Soft 031 & 032)
COM#1
COM#2
COM#3
COM#4
COM#5

Advertisement

loading

This manual is also suitable for:

Grz200