Input
Command "PLC-Open-Control" with ILK†
(PLC#4 connection point)
511001 800201EE31
DEV01_OP_INTERLOCK
Command "PLC-Open-Control" without ILK†
(PLC#5 connection point)
511001 800201EE30
DEV01_OP_COMMAND
ILK† condition ("Open") passed
DPSY01-Open
User configurable condition
(PLC#3 connection point)
511001 800201EE56
DPSY01IN_TMP_34
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
511001 820201EE5E
DPSY01IN_TMP_44
"DPSY01_FEC_OK_CSF"
(511001 8002011E7E)
Figure 4.2-30 Open operation logic by PLC in DPSY01
†Note: The ILK function can provide the criteria for operation for control of the "Open"
operation.
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative "operate-condition" programmed by the user is required in place of
the signal generated by the original operated-condition logic, connect the
alternative "operate-condition" to the logic shown in Figure 1.10-30 using
connection point #3 "User-configurable condition". That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use "DPSY01IN_TMP_34".
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal "DPSY01_OEX_BO" is issued when Fixlogic is set for the scheme
switch [DPSY01-LGCFEXOT]. If the signal to be issued from the programmed
logic by the user in place of Figure 4.2-20 logic, connect the signal "Operate
completed" generated in the programmed logic to the connection point #2 "User
configurable condition". That is, the set the scheme switch [DPSY01-LGCFEXOT]
to PLC and use "DPSY01IN_TMP_44".
*Note: The user can set the type of the output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting applied
to [DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
Operate logic in DPSY01
DPSY01 function (Function ID: 511001)
Operate Cmd.
with ILK
condition
&
Operation Cmd.
without ILK
condition
[DPSY01-LGCTRCON]
Fixedlogic
Operate condition‡
[DPSY01-LGCFEXOT]
Fixedlogic
[DPSY01-PLSM]*
Var
Fix
Detection of state-change in a device
- 579 -
"
DPSY01_FEC_OK_CS"
(511001 8002011E7E)
1≥
1≥
&
&
&
&
PLC#1
&
1≥
&
PLC#2
&
6F2S1915 (0.46)
Output
"
DPSY01_FEC_OK_CSF"
(511001 8002011E7E)
[DPSY01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"DPSY01_FEX_BO" §§
(511001 8102011DD0)
&
Assign to BOs
To "Wait for a command"
"
DPSY01_EX_CMP
(511001 8002011E93)
Operate Completed
"
DPSY01_EX_FFL
[DPSY01-RST]
(511001 8602011E91)
0
t
1.0s- 100.0s
Operate Failed
††
GRZ200 (Soft 031 & 032)
"
"
††