Single shot scheme for an Arcing fault; fault removed by a backup
(iv)
CB
Figure 2.24-8 shows the single shot scheme for an Arcing fault, but tripping is not executed
due to the failure of the CB#1. Therefore, the operation of the ARC function is reset in the
setting time [TRESET] before the duration of dead timer [TTPAR1] expires. Consequently, the
ARC function determines that the local CB#1 cannot be tripped to clear the fault.
Fault current
Closed
CB#1 Status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1 SHOT1
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
ARC1 CLOSE
COMMAND
CB1 ALLPH
Closed
CLOSE
Open
ARC1 CLOSE SUCCESS
ARC1 CLOSE FAIL
ARC1 FT
Reset
ARC RESET
Figure 2.24-8 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; remote CB† tripped
†Note: the fault is removed by the tripping of the CB at the remote end; hence, the fault
current will no longer flow.
Multi shot scheme for Permanent fault
(v)
Figure 2.24-9 illustrates the multi-shot scheme (S3); triple reclosing of the CB#1 by the ARC
function is required and executed correctly. However, the ARC function determines that the
fault is permanent as the fault persists after the third tripping (i.e. the shot counter logic
reaches its maximum value and the fault persists). Consequently, the ARC function moves to
the final trip (ARC1 FT) stage so that the ARC will not issue an 'ARC1 CLOSE COMMAND'
signal hereafter.
Fault cleared by tripping the backup CB at the remote end†
CB at the local end fails to open
Dead time [TTPAR1]
[TRESET]
)
- 353 -
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)