Download Print this page

Toshiba GR200 Series Instruction Manual page 280

Hide thumbs Also See for GR200 Series:

Advertisement

Setting
2.14.6
OVG(Function ID: 462101)
Setting items
OVG1-EN
OVG2-EN
OVG1
OVG1-Timer
DT
OVG1
TOVG1
OVG1-DPR
IDMT
OVG1
OVG1-DPR
OVG1-TMS
TOVG1R
ORG
OVG1
OVG1-DPR
OVG1-TMS
TOVG1R
OVG1-k
OVG1-a
OVG1-c
Output
OVG1-VTFBlk
OVG1-UseFor
OVG2
OVG2-Timer
DT
OVG2
TOVG2
OVG2-DPR
IDMT
OVG2
OVG2-DPR
OVG2-TMS
TOVG2R
ORG
OVG2
OVG2-DPR
OVG2-TMS
TOVG2R
OVG2-k
OVG2-a
OVG2-c
Output
OVG2-VTFBlk
OVG2-UseFor
Range
Unit
1A rating
5A rating
Off / On
- OVG1 protection scheme switch
Off / On
- OVG2 protection scheme switch
DT / IDMT / Original
- OVG1 delay type
1.0 - 220.0
V OVG1 threshold
0.00 - 300.00
s OVG1 operating delay time (in DT mode)
10 - 100
% OVG1 drop-out/pick-up ratio
1.0 - 220.0
V OVG1 threshold
10 - 100
% OVG1 drop-out/pick-up ratio
0.010 - 100.000
- OVG1 time multiplier (in IDMT mode)
0.0 - 300.0
s OVG1 definite time reset delay
1.0 - 220.0
V OVG1 threshold
10 - 100
% OVG1 drop-out/pick-up ratio
0.010 - 100.000
- OVG1 time multiplier (in ORG mode)
0.0 - 300.0
s OVG1 definite time reset delay
0.00000 - 500.00000
- OVG1 user original curve coefficient
0.00000 - 10.00000
- OVG1 user original curve coefficient
0.00000 - 10.00000
- OVG1 user original curve coefficient
Non / Block
- OVG1 operation block by VTF
Trip / Alarm
- OVG1 used for trip or alarm
DT / IDMT / Original
- OVG2 delay type
1.0 - 220.0
V OVG2 threshold
0.00 - 300.00
s OVG2 operating delay time (in DT mode)
10 - 100
% OVG2 drop-out/pick-up ratio
1.0 - 220.0
V OVG2 threshold
10 - 100
% OVG2 drop-out/pick-up ratio
0.010 - 100.000
- OVG2 time multiplier (in IDMT mode)
0.0 - 300.0
s OVG2 definite time reset delay
1.0 - 220.0
V OVG2 threshold
10 - 100
% OVG2 drop-out/pick-up ratio
0.010 - 100.000
- OVG2 time multiplier (in ORG mode)
0.0 - 300.0
s OVG2 definite time reset delay
0.00000 - 500.00000
- OVG2 user original curve coefficient
0.00000 - 10.00000
- OVG2 user original curve coefficient
0.00000 - 10.00000
- OVG2 user original curve coefficient
Non / Block
- OVG2 operation block by VTF
Trip / Alarm
- OVG2 used for trip or alarm
- 259 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
Off
Off
DT
20.0
1.00
100
20.0
100
1.000
0.0
20.0
100
1.000
0.0
0.00000
0.00000
0.00000
Non
Trip
DT
20.0
1.00
100
20.0
100
1.000
0.0
20.0
100
1.000
0.0
0.00000
0.00000
0.00000
Non
Trip