Scheme logic
2.8.3
Figure 2.8-2 shows the scheme logic for THM. THM has two thresholds; threshold "A" is used
for alarming, threshold "T" for tripping. The name of the output signal for the alarm is termed
THM-OPT-ALARM and that of the output signal for tripping is termed "THM-OPT-TRIP".
The threshold level for the alarm is set using setting [THM-Alarm] as a percentage of the
tripping threshold. The alarm signal is disabled when Off is set for scheme switch [THMA-EN].
The trip signal is prevented when Off is set for scheme switch [THMT-EN]. PLC signals
THMA_BLOCK and THMT_BLOCK are used to block the operation of THM.
8000011C23
A
8100021C23
THM
B
THMA-EN
ON
THMT-EN
ON
800001EBB0 THMA_BLOCK
810002EBB0 THMT_BLOCK
THMA-UseFor
When wishing to have a test about pre-load current (Ip), the user should set a test value for
the setting [THM-IP] followed by setting [THM-Test]=On.
8000011B60
&
&
8100021B60
&
&
1
1
Trip
Alarm
Figure 2.8-2 THM Logic
8300021B23
≥1
8400011B23
&
&
- 214 -
6F2S1915 (0.46)
To TRC
THM-OPT-TRIP
THM-OPT-ALARM
THM-ARC-BLOCK
GRZ200 (Soft 031 & 032)