Input
Command "Remote-P1-Control"
513001_7004016D08
DEV01_CONTROL_REQ
ILK† condition ("P1") passed
TPOS1-P1
User configurable condition
(PLC#1 connection point)
513001 800401EE56
TPOS01IN_TMP_27
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
513001 820401EE5E
TPOS01IN_TMP_38
Figure 4.9-27 Operate 'P1-control' from the remote-end in TPOS01
†Note: The ILK function can provide the operation criteria for "P1" control.
‡Note: An "operate condition" signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative "operate-condition" signal is required, it can be programmed by the
user and used to replace the signal the signal generated by the original operate-
condition logic. The alternative "operate-condition" can be connected to the above
logic using connection point #1 "User configurable condition" That is, set the
scheme switch [TPOS01-LGCTRCON] to PLC and use "TPOS01IN_TMP_27".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of the output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
Note: To identify the input and output signal-points of the P1-control in the other TPOS
††
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
‡‡Note: The "Operate failed" signal is issued when the state-change is not detected when
the time set by the [TPOS01-RST] has been reached.
§§Note: The signal "TPOS01-PIEX-BO" is issued when Fixlogic is set for scheme switch
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
"
TPOS01_P1EC_OK_CSF"
(513001 8004011E7E)
Operate Cmd.
with ILK
condition
&
Operate Cmd.
without ILK
condition
[TPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[TPOS01-LGP1EXOT]
Fixedlogic
[TPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"TPOS01_P1EC_OK_CSF"
(513001 8004011E7E)
- 812 -
"
TPOS01_P1EC_OK_CS"
(5130018004011E81)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2S1915 (0.46)
Output
[TPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"TPOS01_P1EX_BO"
(5130018104011DD0) §§
&
Assign to BOs
To "Wait for a command"
"
TPOS01_EX_CMP
(5130018004011E93)
Operate Completed
"
TPOS01_EX_FFL
[TPOS01-RST]
(513001 8604011E91) ‡‡
0
t
1.0s- 100.0s
Operate Failed
††
GRZ200 (Soft 031 & 032)
"
"