Download Print this page

Toshiba GR200 Series Instruction Manual page 503

Hide thumbs Also See for GR200 Series:

Advertisement

Mapping output data
(ii)
The user should group the GCNT01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS (Figure 3.7-18 illustrates
how to map a signal); it indicates that the signals for the GCNT01 function are required to
map the IEC 61850 communications.
Table 3.7-10 Mapping signals required for GIGO3302 object in GCNT01 function
Object_reference
Ctrl/GGIO3302$ISCSO$origin
Ctrl/GGIO3302$ISCSO$origin
Ctrl/GGIO3302$ISCSO
Ctrl/GGIO3302$ISCSO
Ctrl/GGIO3302$ISCSO
Ctrl/GGIO3302$ISCSO
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850.
Figure 3.7-18 orCat attribute mapped into ISCSO object of GIGO3302
Mapping input data
(iii)
The GCNT01 function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point " GCNT01_CMM_REQ". Table 3.7-11 shows the input-point
"GCNT01_CMM_REQ" and the Object reference "Ctrl/GIGO3302$ISCSO1" ; the user should map
the input-point to the Object reference having attributes CO and CF in FC† . Figure 3.7-19 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; "CO" stands for "Control" in the
functional constraint (FC).
Attribute
Type
orCat
orCategory
orIdent
Octet64
stVal
INT32
q
Quality
t
Timestamp
stSeld
BOOLEAN
Drag and drop
- 482 -
FC
Signal Number
ST
540001300e011D23
ST
5400016A0e011FA7
ST
540001320e011D20
ST
3010013110041005
ST
2003019010001006
ST
540001000E011D91
6F2S1915 (0.46)
Signal Name
GCNT01_CNT_ORCAT
GCNT01_CNT_ORIDENT
GCNT01_CNT_VAL
Qual_Val
SYS_TIME
GCNT01_TMP_01
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200