are shown in Figure 2.1-30(b).
X
LESL-Angle
LESR
LESL
a.
LESL and LESR for ZS
Figure 2.1-30 Load encroachment characteristic
The load encroachment element can operate for the command protection functions (ZCS
and ZCG elements) when the user sets Block for the scheme switches [ZCS-LEBlk] and [ZCG-
LEBlk]. We shall see the ZCS and ZCG functions later.
Fail safe function
(iii)
Both ZS and ZG provide overcurrent elements, which can be used for fail-safe operation.
For example, an overcurrent element is provided in Z*S, termed Z*S-OCFS-EN. The
option of Z*S-OCFS-EN operation can be included when On is set for the scheme switch [Z*S-
OCFS-EN], the overcurrent element is subject to the setting of [OCF*S] in Z*S. The setting
value is chosen between 0.02–5.00 A (1 A rating) or 0.10–25.00 A (5 A rating).
Similarly, ZG is also provided with overcurrent elements for fail-safe operation. If On is
set for the scheme switch [Z*G-OCFS-EN], the overcurrent element is subject to the setting of
[OCF*G] in Z*G.
Definite time delay operation
(iv)
In accordance with the location of the fault, the timing of trip signals can be adjusted with
delayed timers. For instance, a delay timer in Z*S tripping can be set by applying a time delay
setting using [TZ*S] whose value can be chosen between 0.00–100.00s. Similarly, for ZG
delayed timers can be applied using [TZ*G].
LEGL-Angle
LESR-Angle
R
b.
- 55 -
X
LEGR
LEGL
LEGL and LEGR for ZG
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)
LEGR-Angle