4.1-17.
2.
Set scheme switch [SPOS01-LGEXFFCT] to Fixedlogic.
Replacing the original logic
If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connection point "User configurable condition":
1.
Connect the user-customized logic using "SPOS01IN_TMP_41", listed as PLC#2 in
Table 4.1-17.
2.
Set scheme switch [SPOS01-LGEXFFCT] to PLC.
Note: The user must program PLC logic "Control hierarchy condition". The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point "SPOS01IN_TMP_28" in
Figure 4.1-29.
Note: The output of the operate condition logic is provided separately for On-execution
and for Off-execution. To see the outputs, refer to Table 4.1-18.
Command blocking*1
Double Command Blocking detected*2
Other devices traveling detected*3
Function "Automatic sequence control" is in progress
ASEQ_MULTI_SEL
Tripping *4 ("General trip")
[SCDEN]*8
Additional condition (PLC#1 connection point)
510001 800101EE61
SPOS01IN_TMP_31
User configurable operate condition (PLC#2 connection
point)
510001 810101EE66
SPOS01IN_TMP_41
Control hierarchy (e.g. 43RL) (PLC connection point)*9
510001 820101ED50
SPOS01IN_TMP_28
IED serious error detected
Figure 4.1-29 Operate condition logic for ON/OFF in SPOS01
Note: "Command blocking" disables any operation except for itself; "Command
1
Blocking" is implemented as "CBK"in software switch controller (SOFTSW).The
IEC 61850 standard defines communication blocking as "CmdBlk". For more
SPOS01 function (Function ID: 510001)
CBK_STATE
DCB RCV OR
Traveling OR
Unmatched condition detected *5
Event suppression detected *6
= SPOS01_F_QLT_SPP
GEN. TRIP
BI board connection error detected*7
= SPOS01_F_BI_ERR
Command "ON-control" received
Command "OFF control" received
SPOS01_STATE
(510001 0001011001)
OFF
[SPOS01- LGEXFFCT]
Fixedlogic
Users must setup this condition correctly
SERI_ERR
[SPOS01-CTREN]
On
1≥
(510001 810101F59)
(510001 820101F5A)
&
&
received
Same Directional
Controlling Event
- 528 -
6F2S1915 (0.46)
1≥
&
&
To selection logic
Operate condition
&
&
GRZ200 (Soft 031 & 032)