Toshiba GR200 Series Instruction Manual page 376

Hide thumbs Also See for GR200 Series:

Advertisement

OFF
FT
SPAR
TPAR
SPAR&TPAR
MPAR
ARC1-MODE
ORIGINAL
800001EBB0
ARC1_MODE-OFF
810001EBB1
ARC1_MODE-FT
820001EBB2
ARC1_MODE-SPAR
830001EBB3
ARC1_MODE-TPAR
800001EBB7
ARC1_MODE-S&T
850001EBB5
800001EBB7
ARC1-MODE-MPAR
860001EBB6
800001EBB7
ARC1_MODE-ORG
Signal '1' is generated when there is no contradiction between the
various signals, that is only one signal is picking up.
CB1 F.BRIDGE
800001EBB8
READY
When FT is selected, the ARC function send 'CB1_BRIDGE' signal for the TRC function
to be the CB being tripped in three-phases, regardless of the condition of the tripped phase,
the operation of respective protection elements, and the ARC settings; the ARC function does
not operate (i.e., ARC1-FT).
When TPAR is selected, the TRC and the ARC functions operate by the rule that the CB
is tripped in three-phases and can be reclosed. That is, 'CB1_BRIDGE' signal is sent for the
TRC function so that the CB will be tripped in three-phases forcibly even if a GEN.TRIP-A
(TRIP COMMAND-A) signal is only generated in the TRC function (as well as GEN.TRIP-B
and GEN.TRIP-C). Note the CB will be tripped in three-phases forcibly, even if a single-phase
fault is detected and instructed a single-phase tripping by the relay applications.
&
&
&
&
&
&
&
1
&
&
&
&
&
&
&
Figure 2.24-10 ARC1-MODE input logic
- 355 -
≥1
≥1
ARC1-MODE=SPAR
≥1
ARC1-MODE=TPAR
≥1
ARC1-MODE=S&T
≥1
ARC1-MODE=SPAR+S&T
≥1
≥1
ARC1-MODE=MPAR
≥1
ARC1-MODE=NO-OFF
≥1
≥1
ARC1-MODE=ON
ARC1-MODE=OFF
ARC1-MODE=ORG
8800011B62
≥1
6F2S1915 (0.46)
Condition
Start
Initiation
Original
To TRC
CB1_BRIDGE
GRZ200 (Soft 031 & 032)