operation signals are summarized by the "OR" logic of Figure 2.23-4. This logic has selection
scheme that is prescribed by scheme switch [FL-Dir]. As a result, the FL can record the current
and voltage data if the fault occurs in either the forward direction or the reverse direction.
Note: For the FL calculation, it is required to fit the direction of the FL calculation
between the FL and other protection function. For example, if Forward is set for
the scheme switch [FL-Dir], user should set Forward for the respective scheme
switches [Z*S-DIR], [Z*G-DIR] and [OC*]. If the contradiction is found in the
direction, the FL does not run. Additionally, it is required to check that the
respective settings of the protection functions are placed properly. For further
information, see section 2.23.3(iii).
Forward
Z1S DIR
Reverse
Z1S
Forward
Reverse
Z1XS DIR
Z1XS
Forward
Reverse
Z2S DIR
Z2S
Forward
Reverse
Z3S DIR
Z3S
Operation signal of ZS elements
Forward
Z1G DIR
Reverse
Z1G
Forward
Reverse
Z1XG DIR
Z1XG
Forward
Reverse
Z2G DIR
Z2G
Forward
Reverse
Z3G DIR
Z3G
Operation signal of ZG elements
Forward
OC1-Dir
Reverse
OC1
Forward
Reverse
OC2-Dir
OC2
Operation signal of OC elements
ZC
Operation signal of ZCS and ZCG elements
DIFL
RDIF
≥1
DIFG
RDIFG
Operation signal of DIF elements
310022EC60
FLZ_RecF
310022EC64
FLAZ_RecF
310022EC61
FLZ_RecF
310022EC65
FLAZ_RecR
PLC signals
Figure 2.23-4 Data recording start (Current and voltage data saved)
≥1
≥1
≥1
≥1
≥1
≥1
Forward
≥1
Reverse
≥1
- 329 -
≥1
Forward
&
≥1
Reverse
&
Forward
FL-DIR
Reverse
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)
The data
(current and
voltage) saved
by the
operation of
elements of
protection
functions.
The data
(current and
voltage) saved
by the
operation of
elements of
protection
functions.