are required to be mapped for IEC 61850 communication
Object_reference
Ctrl/LLN0$LEDRs$origin
Ctrl/LLN0$LEDRs$origin
Ctrl/LLN0$LEDRs
Ctrl/LLN0$LEDRs
Ctrl/LLN0$LEDRs
Ctrl/LLN0$LEDRs
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850.
Figure 3.6-13 orCat attribute mapped for LEDRs object of LLN0
Mapping input data
(iii)
The LEDR function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point "LED 01_CONTROL_REQ" to the IEC61850 communication . Table
3.6-6
shows
"Ctrl/LLN0$LEDRs" ; the user should map the input-point to the Object references having
attributes CO and CF† . Figure 3.6-14 shows how to map a signal.
†Note: The attribute is defined in the IEC 61850; "CO" stands for "Control" and "CF"
stands for "Configuration" in the functional constraint (FC).
Table 3.6-5 Mapping signals for SPC object
Attribute
orCat
orCategory
orIdent
Octet64
stVal
BOOLEAN
q
Quality
t
Timestamp
stSeld
BOOLEAN
the
input-point
"LED01_CONTROL_REQ"
Type
FC
Signal Number
ST
5280013107011008
ST
5280016A07011009
ST
5280013107011EA1
ST
3010013110041005
ST
2003019010001006
ST
5280010007011001
- 463 -
6F2S1915 (0.46)
Signal Name
LEDR01_ORCAT
LEDR01_ORIDENT
LED_RST_CMD
Qual_Val
SYS_TIME
LEDR01_STSELD
and
the
Object
reference
GRZ200 (Soft 031 & 032)