points "DPSY01_OEX_BO" and "DPSY01_FEX_BO"; as a result, the "Operate command
Closing" and the "Operate command Open" signals are issued at BO3 and BO4 respectively.
Operate logic in DPSY01
"
DPSY01_OEX_BO
(511001 8202011DD3)
Operate logic for
"Operate command
Closing"
To contact health
check
"
DPSY01_FEX_BO
(511001 8102011DD0)
Operate logic for
"Operate command
Open"
To contact health
check
Figure 4.2-44 Example of operate commands connected with BO2 and BO3 at IO#1
†Note: Table 4.2-36 shows the remaining signals excepting "DPSY01_OEX_BO" and
"DPSY01_FEX_BO".
Contact health check
(iv)
The DPSY01 function has a contact health check feature for the BO circuits; hence, the user is
able to connect an output signal to the contact health check function when Fixedlogic is set for
scheme switch [DPSY01-LGXFEOT]†. Consequently, the DPSY01 function can determine
whether the signal has been successfully output from the BO. If a failure is reported, the
DPSY01 function determines that the signal has not been output successfully to the BO; then,
the Closing- or Open-command is canceled immediately and the DPSY01 function returns to
the "Wait for a command" stage.
†Note: Table 4.2-38 shows settings for the health check feature in the DPSY02 function.
"
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO3
"
200B01 310202E11D
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO4
200B01 310203E11D
- 594 -
BO3 and BO4 circuit at IO#1 (Function ID: 200B01)
(200B01_8202021112)
≥1
≥1
&
On
[BO3_CPL]
&
Off
BO3_SOURCE
(
200B01_8302031112)
≥1
≥1
&
On
&
[BO4_CPL]
Off
BO4_SOURCE
6F2S1915 (0.46)
Terminal and
wire
Operate
"
"
BO3
command
Closing to
the device
DRIVER
BO3
"
"
BO3-RB
(
200B01_8202021113)
To contact health
check
Operate
"
"
BO4
command
Open to the
device
DRIVER
BO4
"
"
BO4-RB
(
200B01_8302031113)
To contact health
check
GRZ200 (Soft 031 & 032)