Toshiba GR200 Series Instruction Manual page 649

Hide thumbs Also See for GR200 Series:

Advertisement

†Note: To identify the input and output signals of the other SOFTSW logics, see Table
4.3-12, Table 4.3-13, and Table 4.3-14.
‡Note: "operate condition" signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
Receiving "operate command On" using PLC logic
(v)
Figure 4.3-19 shows the logic when an "Operate command (PLC-ON-Control)" signal is applied
to the SOFTSW1 logic. The input signal is generated using the user-programmed PLC logic;
the user can connect the signal for the PLC connection point "S4301_CHG_TO_ON".
Input
ON-control command
(PLC connection point #1)
522001 850A04EDE1
S4301_CHG_TO_ON
ASEQ function§" is in progress
ASEQ_MULTI_SEL
Figure 4.3-19 'ON' Operation logic using PLC logic†
†Note: To identify the input and output signal-points of the other SOFTSW logics, see
Table 4.3-3, Table 4.3-13, Table 4.3-15, Table 4.3-16, and Table 4.3-17.
‡Note: "operate condition" signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
Receiving "operate command Off" using PLC logic
(vi)
Figure 4.3-20 shows the logic when an "Operation command (PLC-Off-Control)" signal is
applied to the SOFTSW1 logic. The input signal is generated using the user-programmed PLC
logic; the user can connect the signal for the PLC connection point "S4301_CHG_TO_OFF".
Operate logic in SOFTSW1
SOTFSW1 function (Function ID: 522001)
Operate Command
Operate condition‡
522001_810A041D03
S4301_ST_ON
- 628 -
"S4301_OEC_CHG_PLC"
(522001_8C0A041F5D)
&
"S4301_EX_SS"
(522001_870A041F62)
&
"S4301_PLC_CTRL_FAIL"
(522001_870A041F62)
0
t
&
1.0s
6F2S1915 (0.46)
Output
OFF to ON
Operate completed
Operate failed
d
GRZ200 (Soft 031 & 032)