Chapter 6 Operation and Troubleshooting
>
6.5 Troubleshooting
When the general status of GUI is
Check whether the miniSAS cables (for drive enclosures) are connected in the correct order.
If not, reconnect the miniSAS cables in the following order.
When the FAULT LED blinks
Check the General Status in GUI. A General Status of
DX60/DX80 contains a component that requires preventive maintenance.
Use the Storage System Status screen's device tree to check the detailed information on the
component whose
Refer
P3AM-3042-03ENZ0
ETERNUS DX60/DX80 Disk storage system User Guide
Procedure
1
Press the controller enclosure's Power Switch for four seconds or more to turn off the
ETERNUS DX60/DX80.
Drive enclosures with no miniSAS cables connected will remain on.
2
Connect the miniSAS cable while the drive enclosure is on.
3
Press the controller enclosure's Power Switch to turn on the ETERNUS DX60/DX80.
Procedure
1
Press the controller enclosure's Power Switch for four seconds or more to turn off the
ETERNUS DX60/DX80, and turn off the AC power.
2
Re-connect the miniSAS cable.
3
Make sure that power is being supplied, then turn the ETERNUS DX60/DX80 on.
image is on, and contact your maintenance engineer.
When checking the general status and detailed information on products via
CLI, refer to "ETERNUS DX60/DX80 Command Line Interface (CLI) User's
Guide".
"ETERNUS DX60/DX80 Command Line Interface (CLI) User's Guide"
180
End of procedure
End of procedure
indicates that the ETERNUS
Copyright 2009 FUJITSU LIMITED