ABB ACS800 Series Firmware Manual page 118

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

106
No.
Name/Value
62.13 MAX TAPER/% TAPER
0...100%
62.14 MAX DANCER TRAVEL
1.0 ...2500.0 mm
1.0 ...2500.0 inch
62.15 CENTER OFFSET
-1250.0...1250.0 mm
-1250.0...1250.0 inch
62.23 WEB 2 SELECT
NOT SEL
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
FIELDBUS
62.24 P-GAIN 2 MIN
0.01...1000.00 K
62.25 P-GAIN 2 MAX
P-GAIN 2 MIN...1000.00 K Setting range.
62.26 INTEG TIME 2
10...10000 ms
Actual signals and parameters
Description
This parameter is only used if the drive is used to control the dancer
loading. If the drive is not controlling the dancer loading
DANCER LOAD REF is not sent to an AO) then this parameter can be
ignored.
If MAX TAPER/%TAPER is not 0%,
decreases as
03.13
ROLL DIAMETER increases. At
DIAMETER, the taper setpoint is 100%. At
DIAMETER, the taper setpoint is the 62.13 MAX TAPER/%TAPER *
the value from
62.12
TAPER REF SELECT.
Setting range.
Set to the total mechanical travel of the dancer; the dancer
automatically regulates to the midpoint of this distance. Should it be
desired to have the dancer regulate to something other than midpoint,
enter this offset value into
Setting range.
Desired offset distance from dancer null value (to which dancer
regulates).
Setting range.
Sets or selects the activation signal source for switching the gain and
integration time for the dancer PI regulator.
Not selected. P-GAIN 1 and INTEG TIME 1 are used (62.01...62.03). 1
Digital input DI2 = 1 selects P-GAIN 2 and INTEG TIME 2
(62.24...62.26).
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2. Instead of a digital input, the command comes from
06.03
DATASET 1 WORD 3 bit 01. See chapter
Optional minimum proportional gain of the dancer PI regulator.
Setting range.
Optional maximum proportional gain of the dancer PI regulator.
Optional integration time of the dancer PI regulator.
Setting range.
03.04
DANCER LOAD REF
65.01
65.02
MAX ROLL
62.15
CENTER OFFSET.
Fieldbus
FbEq
(03.04
MIN CORE
1 = 1%
10 = 1 mm
10 = 1 inch
10 = 1 mm
10 = 1 inch
2
3
4
5
6
7
8
9
10
11
12
13
control.
100 = 1 K
100 = 1 K
1 = 1 ms