Analog Outputs - ABB ACS800 Series Firmware Manual

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

No.
Name/Value
14.11 RO3 TON DELAY
14.12 RO3 TOFF DELAY
14.13 RO4 POINTER
14.15 RO5 POINTER
14.17 RO6 POINTER
14.19 RO7 POINTER

15 ANALOG OUTPUTS

15.01 AO1 POINTER
-255.255.31...+255.255.31
/ C.-32768...C.32767
15.03 MINIMUM AO1
0 mA
4 mA
10 mA
15.04 FILTER AO1 ms
0 ...10000 ms
15.05 NOM VALUE AO1
0...65535
15.06 AO2 POINTER
15.08 MINIMUM AO2
15.09 FILTER AO2 ms
15.10 NOM VALUE AO2
15.11 AO3 POINTER
15.13 MINIMUM AO3
15.14 FILTER AO3 ms
15.15 NOM VALUE AO3
15.16 AO4 POINTER
15.18 MINIMUM AO4
15.19 FILTER AO4 ms
15.20 NOM VALUE AO4
Description
See
14.03
RO1 TON DELAY.
See
14.04
RO1 TOFF DELAY.
See
14.01
RO1 POINTER.
See
14.01
RO1 POINTER.
See
14.01
RO1 POINTER.
See
14.01
RO1 POINTER.
The analog output signal processing
The analog output is controlled by use of "pointers". This parameter
selects the word that is the desired output. Example:
+.001.002.00 = MOTOR SPEED FILT.
Parameter index or a constant value. See
information on the difference.
Defines the minimum value of the analog output signal AO1.
Zero mA.
Four mA.
Ten mA. 50% offset on 0 to 20 mA for testing or indication of direction. 3
Defines the filtering time constant for analog output AO1.
%
Unfiltered Signal
100
63
Filtered Signal
T
Note: Even if you select 0 s as the minimum value, the signal is still
filtered with a time constant of 10 ms due to the signal interface
hardware. This cannot be changed by any parameters.
Filter time constant
When the value of the signal selected in
equals this parameter, the output = 20 mA.
Setting range.
See
15.01
AO1 POINTER.
See
15.03
MINIMUM AO1.
See
15.04
FILTER AO1 ms.
See
15.05
NOM VALUE AO1.
See
15.01
AO1 POINTER.
See
15.03
MINIMUM AO1.
See
15.04
FILTER AO1 ms.
See
15.05
NOM VALUE AO1.
See
15.01
AO1 POINTER.
See
15.03
MINIMUM AO1.
See
15.04
FILTER AO1 ms.
See
15.05
NOM VALUE AO1.
10.05
EXT1 STRT PTR for
-t/T
O = I · (1 - e
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
t
15.01
AO1 POINTER 1
Actual signals and parameters
75
FbEq
1 = 1 s
1 = 1 s
-
-
-
-
-
1
2
1 = 1 ms
10 = 1
-
1...3
1 = 1 ms
10 = 1
-
1...3
1 = 1 ms
10 = 1
-
1...3
1 = 1 ms
10 = 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-u2Acs800-u7Acs800-u4

Table of Contents