ABB ACS800 Series Firmware Manual page 177

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

Warning
Cause
MOD CHOKE T
Overtemperature in choke of liquid cooled R8i
inverter module.
(FF89)
02.17 AW 3 bit 13
MOT CUR LIM
Drive limits motor current according to current
limit defined by parameter 20.03.
(2300)
MOTOR STALL
Motor is operating in stall region due to e.g.
excessive load or insufficient motor power.
(7121)
02.16 AW 2 bit 09
(programmable
Fault Function
30.10)
MOTOR STARTS
Motor Identification Run starts. This warning
belongs to ID Run procedure.
(FF34)
MOTOR TEMP
Motor temperature is too high (or appears to be
too high) due to excessive load, insufficient
(4310)
motor power, inadequate cooling or incorrect
02.15 AW 1 bit 03
start-up data.
(programmable
Fault Function
30.04...30.09)
MOTOR 1 TEMP
Measured motor temperature has exceeded
alarm limit set by parameter 35.02.
(4312)
MOTOR 2 TEMP
Measured motor temperature has exceeded
alarm limit set by parameter 35.05.
(4313)
MOT POW LIM
Drive limits motor power according to limits
defined by parameters
(FF86)
MOT TORQ LIM
Drive limits motor torque according to
calculated motor pull-out torque limit and
(FF85)
minimum and maximum torque limits defined
by parameters
PANEL LOSS
Control panel selected as active control
location for drive has ceased communicating.
(5300)
20.11
and 20.12.
20.13
and 20.14.
What to Do
Check inverter fan.
Check ambient temperature.
Check liquid cooling system.
Reduce load or increase ramp time.
Increase parameter
20.03
Check Fault Function parameters.
Check motor load and drive ratings.
Check Fault Function parameters.
Wait until drive indicates that motor
identification is completed.
Check motor ratings, load and cooling.
Check start-up data.
Check Fault Function parameters.
Check value of alarm limit.
Check that actual number of sensors
corresponds to value set by parameter.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of alarm limit.
Check that actual number of sensors
corresponds to value set by parameter.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Informative alarm
Check parameter
20.11
and
Check Fault Function parameters.
Informative alarm
Check parameter
20.13
and
Check panel connection (see appropriate
hardware manual).
Check control panel connector.
Replace control panel in mounting platform.
Check Fault Function parameters.
165
value.
20.12
settings.
20.14
settings.
Fault tracing