ABB ACS800 Series Firmware Manual page 138

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

126
No.
Name/Value
PUSH
DELETE
PROTECT
UNPROTECT
83.03 EDIT BLOCK
0...15
83.04 TIMELEVEL SEL
12 ms
100 ms
1000 ms
83.05 PASSCODE
Actual signals and parameters
Description
Shifts the block in location defined by
following blocks one location up. A new block can be placed in the
emptied location by programming the Block Parameter Set as usual.
Example: A new block needs to be placed in between the current
block number four (parameters 84.20...84.25) and five (parameters
84.25...84.29).
In order to do this:
- Shift the program to the editing mode by
- Select location number five as the desired location for the new block
by
83.03
EDIT BLOCK.
- Shift the block in location number 5 and the following blocks one
location forward by 83.02 EDIT COMMAND (selection PUSH).
- Program the emptied location number 5 by parameters
84.25...84.29 as usual.
Deletes the block in location defined by
the following blocks one step down.
Activation of the Adaptive Program protection. Activate as follows:
- Ensure the Adaptive Program operation mode is RUN or STOP
(83.01
ADAPT PROG CMD).
- Set the passcode
(83.05
- Change 83.02 EDIT COMMAND to PROTECT.
When activated:
- All parameters in group 84 excluding the block output parameters
are hidden (read protected).
- It is not possible to switch the program to the editing mode
ADAPT PROG CMD).
-
83.05
PASSCODE is set to 0.
Inactivation of the Adaptive Program protection. Inactivate as follows:
- Ensure the Adaptive Program operation mode is RUN or STOP
(83.01
ADAPT PROG CMD).
- Set the passcode
(83.05
- Change 83.02 EDIT COMMAND to UNPROTECT.
Note: If the passcode is lost, it is possible to reset the protection also
by changing the application macro setting
MACRO).
Defines the block location number for the command selected by
83.02
EDIT COMMAND.
Block location number.
Selects the execution cycle time for the Adaptive Program. The setting
is valid for all blocks.
12 milliseconds
100 milliseconds
1000 milliseconds
Sets the passcode for the Adaptive Program protection. The passcode
is needed at activation and inactivation of the protection. See
EDIT COMMAND.
83.03
EDIT BLOCK and the
83.01
ADAPT PROG CMD.
83.03
EDIT BLOCK and shifts
PASSCODE).
PASSCODE).
(99.02
APPLICATION
FbEq
2
3
4
(83.01
5
1 = 1
1
2
3
83.02