164
Warning
Cause
ID RUN
Motor identification Run is on.
(FF35)
ID RUN SEL
Motor Identification Run is selected, and drive
is ready to start ID Run. This warning belongs
(FF33)
to ID Run procedure.
IN CHOKE TEMP
Excessive input choke temperature
(FF81)
INV CUR LIM
Internal inverter current or power limit has
been exceeded.
(2212)
INV DISABLED
Optional DC switch has opened while unit was
stopped.
(3200)
INV OVERTEMP
Converter module temperature is excessive.
(4290)
IO CONF
Input or output of optional I/O extension or
fieldbus module has been selected as signal
interface in control program but communication
to appropriate I/O extension module has not
been set accordingly.
MACRO CHANGE
Macro is restoring or User macro is being
saved.
(FF69)
MOD BOARD T
Overtemperature in AINT board of inverter
module.
(FF88)
Fault tracing
What to Do
Wait until drive indicates that motor
identification Run is completed.
Press Start key to start Identification Run.
Stop drive. Let it cool down.
Check ambient temperature.
Check that fan rotates in correct direction and
air flows freely.
Reduce load or increase ramp time.
Limit inverter actual power or decrease line-
side converter reactive power generation
reference value (parameter 95.06).
Check Fault Function parameters.
Close DC switch.
Check AFSC-0x Fuse Switch Controller unit.
Check ambient temperature. If it exceeds
40 °C, ensure that load current does not
exceed derated load capacity of drive. See
appropriate hardware manual.
Check that ambient temperature setting is
correct (parameter 95.10).
Check converter module cooling air flow and
fan operation.
Cabinet installation: Check cabinet air inlet
filters. Change when necessary. See
appropriate hardware manual.
Modules installed in cabinet by user: Check
that cooling air circulation in cabinet has been
prevented with air baffles. See module
installation instructions.
Check inside of cabinet and heatsink of
converter module for dust pick-up. Clean when
necessary.
Check Fault Function parameters.
Check parameter group
98 OPTION
MODULES.
Wait until drive has finished task.
Check inverter fan.
Check ambient temperature.