ABB ACS800 Series Firmware Manual page 17

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

-motor nominal power
...
Range: 0
9000 kW
When the motor data has been entered, a warning appears. It
indicates that the motor parameters have been set, and the drive is
ready to start the motor identification (ID magnetization or ID Run).
Select the motor identification.
The ID Run (STANDARD) should be selected.
For more information, see subsection
DIRECTION OF ROTATION OF THE MOTOR
Check the direction of rotation of the motor.
- Press ACT to get the status row visible.
- Increase the speed reference from zero to a small value by pressing REF and
then the arrow keys (
- Press
to start the motor.
- Check that the motor is running in the desired direction.
- Stop the motor by pressing
To change the direction of rotation of the motor:
- Disconnect input power from the drive and wait 5 minutes for the
intermediate circuit capacitors to discharge. Measure the voltage
between each input terminal (U1, V1 and W1) and ground with a
multimeter to ensure that the frequency converter is discharged.
- Exchange the position of two motor cable phase conductors at the
motor terminals or at the motor connection box.
- Verify your work by applying mains power and repeating the
check as described above.
How to perform the ID Run
,
,
or
).
.
1
99 START-UP DATA
09 MOTOR NOM POWER
[ ]
1
** WARNING **
ID MAGN REQ
1
99 START-UP DATA
10 MOTOR ID RUN
on page 7.
[STANDARD]
1
L->[xxx] rpm
FREQ
CURRENT
POWER
5
->
0.0 rpm
O
->
0.0 rpm
O
->
0.0 rpm
O
I
xxx Hz
xx A
xx %
forward
direction
reverse
direction
Start-up