No.
Name/Value
STD MODBUS
98.03 DI/O EXT MODULE 1
NDIO
NO
RDIO-SLOT1
RDIO-SLOT2
RDIO-DDCS
98.04 DI/O EXT MODULE 2
NDIO
NO
RDIO-SLOT1
RDIO-SLOT2
RDIO-DDCS
Description
The drive communicates with a Modbus controller via the Modbus
Adapter Module (RMBA) in option slot 1 of the drive. See also group
52 STANDARD
MODBUS.
Activates the communication to the digital I/O extension module 1
(optional) and defines the type and connection interface of the
module.
Communication active. Module type: NDIO module. Connection
interface: Fibre optic DDCS link. DI7 and DI8 are from this module.
DI9 and DI10 are from a second module.
Note: Module node number must be set to 2. For directions, see
Installation and Start-up Guide for NTAC-0x/NDIO-0x/NAIO-0x
Modules (Code: 3AFY58919730 [English]).
Inactive.
Communication active. Module type: RDIO. Connection interface:
Option slot 1 of the drive. DI7 through DI9 are from this module. DI10
is from a second module.
Communication active. Module type: RDIO. Connection interface:
Option slot 2 of the drive. DI7 through DI9 are from this module. DI10
is from a second module.
Communication active. Module type: RDIO. Connection interface:
Optional I/O module adapter (AIMA) that communicates with the drive
through a fibre optic DDCS link. DI7 through DI9 are from this module.
DI10 is from a second module.
Note: Module node number must be set to 2. For directions, see
User's Manual for RDIO Module (Code: 3AFE64485733 [English]).
Activates the communication to the digital I/O extension module 2
(optional) and defines the type and connection interface of the
module.
Communication active. Module type: NDIO module. Connection
interface: Fibre optic DDCS link. If
NDIO, DI9 and DI10 are from this module, otherwise only DI10 is.
Note: Module node number must be set to 3. For directions, see
Installation and Start-up Guide for NTAC-0x/NDIO-0x/NAIO-0x
Modules (Code: 3AFY58919730 [English]).
Inactive.
Communication active. Module type: RDIO. Connection interface:
Option slot 1 of the drive. If
DI9 and DI10 are from this module, otherwise only DI10 is.
Communication active. Module type: RDIO. Connection interface:
Option slot 2 of the drive. If
DI9 and DI10 are from this module, otherwise only DI10 is.
Communication active. Module type: RDIO. Connection interface:
Optional I/O module adapter (AIMA) that communicates with the drive
through a fibre optic DDCS link. If
NDIO, DI9 and DI10 are from this module, otherwise only DI10 is.
Note: Module node number must be set to 3. For directions, see
User's Manual for RDIO Module (Code: 3AFE64485733 [English]).
98.03
DI/O EXT MODULE 1 is an
98.03
DI/O EXT MODULE 1 is an NDIO,
98.03
DI/O EXT MODULE 1 is an NDIO,
98.03
DI/O EXT MODULE 1 is an
Actual signals and parameters
133
FbEq
4
1
2
3
4
5
1
2
3
4
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-u2Acs800-u7Acs800-u4

Table of Contents